Type 4 Safety Light Curtain
43
7.2 Overview of All Functions
Emitter Settings
Receiver Settings
Range
Safety mode without contactor
monitoring
Test function
Safety mode with contactor monitoring
Start-up and restart inhibit without
contactor monitoring
Start-up and restart inhibit with
contactor monitoring
Signal output
NOTE!
In order to accept the modified configuration, a test object must be passed through the safe-
ty field (beginning at the sensor connection on the control panel side up to the other end)
within 30 seconds after electrical connection and activation of supply voltage. Interruption is
confirmed by LED DIAG3 at the receiver.
This is always necessary when switching to a “less safe” operating mode:
• From restart inhibit to safety mode
• From contactor monitoring to operation without contactor monitoring
An overview of parameters configuration for the receiver is included in the index
(see section “12.2 Overview of Receiver Parameters Configuration” on page 64)
.