USING YOUR GENERATOR
ECO-MODE SWITCH
This generator is equipped with an Eco-Mode Idle Control Switch
(Fig. 13). Engaging this switch allows the system to regulate the
engine speed and automatically adjust its fuel consumption to
match the required load. When the electrical load changes, the
generator engine will automatically speed up and slow down as
needed. This reduces fuel consumption and noise levels, while
extending runtime and engine’s lifespan.
Keep this switch engaged ONLY when the power load requirement is less than 2550W (75% of the rated watts). Do
not engage the Eco-Mode Switch when the total load is more than 2550W. The generator engine must run at full
speed to supply power for anything over 2550W.
PARALLEL OPERATION
The parallel connection ports (Fig. 14) allow you to connect two
WEN generators to increase the total available electrical power.
The WEN Parallel Connection Kit can be purchased from
wenproducts.com.
Follow the instructions included with your
parallel connection kit for proper installation and operation.
IN CASE OF OVERLOAD
If your generator becomes overloaded from too much drawn
wattage, the overload indicator (red) on the control panel will
light up. Follow the instructions below when an overload occurs:
• When you’re close to overloading the generator, the overload
light will start to flash. Reduce the load by turning off and dis-
connecting your electronic device(s) until the overload light turns
off. Then you may continue to operate your generator.
• When you’ve overloaded the generator, the overload light will stay on and the reset button (Fig. 15) will activate
to cut off the output in 3 to 16 seconds, depending on the load. Reduce the load by turning off and disconnecting
your electrical device(s) until the overload light turns off. Wait about five minutes and then press the activated reset
button to reset the circuit. If no power is produced after resetting, turn off and disconnect all electrical devices and
restart your generator.
CIRCUIT BREAKERS
In addition to the reset button that protects the generator’s main
circuit, the circuit breakers (Fig. 16) protect the individual AC and
DC circuits. The 20-amp AC circuit breaker will activate when the
NEMA 5-20 outlets exceed 20A. The 10-amp DC circuit breaker
will activate when the DC 12V and USB outlets exceed 10A. When
the circuit breaker activates, turn off and disconnect the device
from its respective outlet, and press the circuit breaker to reset.