background image

WEMPE ENI 

secondary clocks interface

2.2  Lights 

All lights are activated only if the so named switch (see above) is set to "ON"! 

      Blue LED: "Power" 
Shows,  that  the  internal  power  regulation  is  up. Wether  the  ENI  is  powered  from  an  ethernet  switch 
(PoE) or an external 24V DC supply, the power is good. 

     Yellow LED: "Net" 

Shows  the  ethernet  connection  and  activity.  If  the  light  is  on,  the  device  is  connected  to  a  working 
ethernet port (hub, switch, router). Flickering shows ethernet activity.  In some cases (e. g. connected 
to a hub) this activities do not necessary regard the ENI itself but can show any network traffic in that 
subnet. 

     Green LED: "State" 

Shows the ENI's operational state through blink codes. Generally the LED blinks at 4 Hz and the code 
is the flash count in 1 second. 

Blink Code per second 

State 

Meaning 

(off) 

INIT 

Can't finish initialization, most likely the device is damaged 

MAC 

No physical network connection 

LINK 

Network up, but doesn't respond to IP requests 

CONN 

Network up, but no IP address, possibly waiting for DHCP 

 (= continous blink)  WAIT 

Network connection configured, waiting for time source 

(on) 

RUN 

Normal synchronized clock operation mode 

     Red LED: "Error" 

Shows the ENI's error state through blink codes. Generally the LED blinks at 4 Hz and the code is the 
flash count in 1 second. 

Blink Code per second 

Error 

Meaning 

(off) 

OK 

No error 

PROTO 

Ethernet packet error in connection to time source 

TOUT 

No update from time source within 2x update interval 

BRIDGE  Clock line output overload / shortcut / disconnection 

Alarm can be reset by pushing the 12h while the "Service" 
switch is "OFF" after the cause is solved 

 (= continous blink)  TEMP 

Temperature out of configured thresholds 

(on) 

INIT 

Can't start initialization, most likely the device is damaged 

(real slow) 

BOOT 

Firmware update mode, no clock operation 

Summary of Contents for 20804/IP

Page 1: ...d and glass frame Geh use Housing Messing hochglanz verchromt brass high gloss chrome plated Abmessungen mm Dimension mm 232 H he 65 232 height 65 Zifferblatt mm Dial mm Aluminium wei 230 aluminium wh...

Page 2: ...mmleiste Terminal block Ersatzteile spare parts TypE T Type IP Art No Beschreibung description ENI v3 WEMPE Ethernet Secondary clock interface Connector RJ45 Ethernet 10Base T IPv4 network cable twist...

Page 3: ...die Buchse am Zeiger etwas zusammengedr ckt werden Setzen Sie danach den Minutenzeiger auf die Minutenachse und ziehen Sie die Stiftschraube M2 der Buchse fest an Es ist darauf zu achten dass zwische...

Page 4: ...ghtly squeezed Then place the minute hand on the minute arbour and tighten the pin screw M2 of the liner Please pay attention that there is enough space between the hands To check this turn the minute...

Page 5: ...ce ENI Ethernet Secondary Clocks Interface Quick Start Guide valid for Hardware Rev 3 0 03 10 2016 Firmware V3 05 05 12 2016 V3 06 22 12 2016 Secondary Clock Ethernet Interface Compatible with Wempe M...

Page 6: ...tatic by default This can be changed to obtain addresses from a DHCP server The DHCP query asks for addresses of NTP servers too If the DHCP server provides them up to two addresses will be mentioned...

Page 7: ...to reconnect the web browser after a few seconds Further ENI configuration can be done on the Master Clock s web interface see it s manual Master Clock Rev Master Clock Software Version1 Select ENI V...

Page 8: ...subnet This option requires a working DHCP server on the same subnet that the ENI is connected to Set_MIN Force the network initialization to use the static IP address 172 16 0 100 which is the facto...

Page 9: ...ng off INIT Can t finish initialization most likely the device is damaged MAC No physical network connection LINK Network up but doesn t respond to IP requests CONN Network up but no IP address possib...

Page 10: ...one user name and one password There is no way to add or delete account names There is no limit in the count of failed logins due to wrong passwords To protect the web interface access against brute...

Page 11: ...s from PC to ENI and back The ping tool on the Tools page of the web interface see ENI user manual can assist Check any blocking features firewall etc at every routing device between ENI and PC Try us...

Page 12: ...2 to set the correct protocol version Check the IP addresses of ENI and masterclock are in the same IP subnet or VLAN The ping tool on the Tools page of the web interface see ENI user manual can assis...

Reviews: