WEMPE 20804/IP Manual Download Page 12

WEMPE ENI 

secondary clocks interface

problem 

possible cause/solution 

The green LED "State" blinks 
continiously (Blink code 4, see 
chapter 2.2). 

OR 

The red LED "Error" shows "Single 
flashing" or "Double flashing" (Blink 
code 1 or 2) 

Clock hands keep showing 12:00, 
Connection type is "WEMPE 
Masterclock 20102, NTP server. 

Communication failure to NTP server. 

Check configured IP addresses of NTP server(s).

If DHCP is enabled, check obtaining IP addresses of NTP
server(s) from the offering DHCP server.

Check IP routes from ENI to configured NTP server and
back. The ping tool on the Tools page of the web interface
(see ENI user manual) can assist.

In case of redundant masterclocks check all of the possible
routes.

Check any blocking features (firewall etc.) at every routing
device between ENI and NTP server(s).

Check the NTP server at the configured IP address(es) are
up and running.

The green LED "State" blinks 
continiously (Blink code 4, see 
chapter 2.2). 

OR 

The red LED "Error" shows "Single 
flashing" or "Double flashing" (Blink 
code 1 or 2, see chapter 2.2). 

Clock hands keep showing 12:00, 
Connection type is "WEMPE 
Masterclock 20100, 20101. 

Communication failure to masterclock. 

Check configured ENI V1 compatibility. See chapter 1.3.2
to set the correct protocol version.

Check the IP addresses of ENI and masterclock are in the
same IP subnet or VLAN. The ping tool on the Tools page
of the web interface (see ENI user manual) can assist.

In case of dynamic VLAN: check the Announce protocol is
switched on (Configuration page of ENI's web interface).

Check any blocking features (firewall etc.) at every routing
device between ENI and masterclock.

Check the route of packets between ENI and the supposed
masterclock device.

Check the web interface of the masterclock, are there any
errors regarding the slaveclock?

Check the time broadcast for the right LAN port at the
masterclock is active.

Movement doesn't step, the red 
LED "Error" shows "Triple flashing" 
(Blink code 3, see chapter 2.2). 

Movement wires are shortcut or interrupted. Sometimes a 
failure of a movement coil itself. Check the wires from ENI to 
the movement. After resolving the cause the movement control 
will not recover automatically. To restart the H-Bridge power 
supply press the "12h" button while the "Service" switch is set 
to "OFF". Most likely the clock hands will then show an 
incorrect time. In this case you need to adjust the hands via the 
web interface (see ENI user manual). 

The red LED "Error" blinks 
continiously (see chapter 2.2) 

Temperature alarm. Check the ENI's environment does not 
exceed the configured alarm threshold (default: 0…70°C). 

For more hints refer to the ENI user manual. 

Summary of Contents for 20804/IP

Page 1: ...d and glass frame Geh use Housing Messing hochglanz verchromt brass high gloss chrome plated Abmessungen mm Dimension mm 232 H he 65 232 height 65 Zifferblatt mm Dial mm Aluminium wei 230 aluminium wh...

Page 2: ...mmleiste Terminal block Ersatzteile spare parts TypE T Type IP Art No Beschreibung description ENI v3 WEMPE Ethernet Secondary clock interface Connector RJ45 Ethernet 10Base T IPv4 network cable twist...

Page 3: ...die Buchse am Zeiger etwas zusammengedr ckt werden Setzen Sie danach den Minutenzeiger auf die Minutenachse und ziehen Sie die Stiftschraube M2 der Buchse fest an Es ist darauf zu achten dass zwische...

Page 4: ...ghtly squeezed Then place the minute hand on the minute arbour and tighten the pin screw M2 of the liner Please pay attention that there is enough space between the hands To check this turn the minute...

Page 5: ...ce ENI Ethernet Secondary Clocks Interface Quick Start Guide valid for Hardware Rev 3 0 03 10 2016 Firmware V3 05 05 12 2016 V3 06 22 12 2016 Secondary Clock Ethernet Interface Compatible with Wempe M...

Page 6: ...tatic by default This can be changed to obtain addresses from a DHCP server The DHCP query asks for addresses of NTP servers too If the DHCP server provides them up to two addresses will be mentioned...

Page 7: ...to reconnect the web browser after a few seconds Further ENI configuration can be done on the Master Clock s web interface see it s manual Master Clock Rev Master Clock Software Version1 Select ENI V...

Page 8: ...subnet This option requires a working DHCP server on the same subnet that the ENI is connected to Set_MIN Force the network initialization to use the static IP address 172 16 0 100 which is the facto...

Page 9: ...ng off INIT Can t finish initialization most likely the device is damaged MAC No physical network connection LINK Network up but doesn t respond to IP requests CONN Network up but no IP address possib...

Page 10: ...one user name and one password There is no way to add or delete account names There is no limit in the count of failed logins due to wrong passwords To protect the web interface access against brute...

Page 11: ...s from PC to ENI and back The ping tool on the Tools page of the web interface see ENI user manual can assist Check any blocking features firewall etc at every routing device between ENI and PC Try us...

Page 12: ...2 to set the correct protocol version Check the IP addresses of ENI and masterclock are in the same IP subnet or VLAN The ping tool on the Tools page of the web interface see ENI user manual can assis...

Reviews: