+86-510-85161517 I [email protected] I www.welsonpower.com
2
Product GeneralIntroduction
2.1
Electrical Prefermance
Items
ES2000
ES2000PLUS
ES5000
Nominal Voltage
51.2Vd.c
51.2Vd.c
51.2Vd.c
Nominal Current
30.0A
30.0A
60.0A
Nominal Capacity
48.0Ah@25
℃
50.0Ah@25
℃
100.0Ah@25
℃
Useable Capacity
43.0Ah@25
℃
45.0Ah@26
℃
90.0Ah@26
℃
Total Energy
2.40KWh
2.56KWh
5.10KWh
Useable Energy*
2.20KWh
2.30KWh
4.60KWh
Nominal Charge/Discharge Power
1.50kW
1.75kW
3.0kWh
Dimension(L*W*H)
500*442*133 mm(3U)
442*500*89mm(2U)
550*442*133 mm(3U)
Weight
27.5Kg
26.0Kg
48.0Kg
Peak Power(Only discharge)
3.5kW for 3 seconds
5.0kW for 3 seconds
Peak Current(Only Discharging)
70A for 3 seconds
100A for 3 seconds
Constant Current(Only discharge)
40.0A
80.0A
Voltage Range
48~56Vd.c
Max. Charge Voltage
57.6V
Max. Recommended DOD (Off-grid)
90%
Efficiency
>97%
Operating Condition
Indoor
Operating Temperature@Charge
0
℃
to +45
℃
Operating Temperature@Discharge
-10
℃
to +55
℃
Operating Humidity
< 60% (No Condensed Water)
Pollution Degree
3
Over Voltage Category
II
Cooling Type
Natural cooling
Case Material
Metal
Color
Black or Grey
Installation
Wall Mounting/Ground Installation/Cabinet
IP rating
IP 20
Max. Number of Parallel or Series
8
Warranty
10 years
Life Span
>15 years
Cycles
>6000@90%DOD
Communication
CAN/RS485
Protection Mode
Dual hardware protection
Battery Protection
Over-current/Over-voltage/Short circuit/Under-voltage/Over-temperature
Safety Certification of Cells
CE+CB
Safety Certification of Module
TUV(IEC 62619, IEC 62040-1,CE)
Hazardous Material Classification
9
Transportation
UN 38.3
Testing conditions based on temperature 25
℃
at the beginning of life.
*Total Energy/Usable Energy measured under specific conditions from WELSON 0.2C CC-CV