6. Setting of parameters
Page 32
106082
– MRF-M2 -E - V0.7 - 23.04.2021
6.5 Level
“I / O test parameters” (o. parameters)
Switch to level
“ I / O test parameter” see section 6.1
Meaning of the parameters
All inputs and outputs of the individual components can be tested in this parameter
level. For this purpose the corresponding relays are set to 'I' or '0'.
Test relay outputs
Range
Def.
Switched-on relays remain switched on until they are
reset manually.
o.1 Test agitator
0 .. 1
0
o.2 Test compressor
0: Relay switched off
1: Relay energized
0 .. 1
0
Test digital input
Select parameter [o.21] with the arrow keys and test as follows:
Press the SET key briefly: '0' or '1' appears in the display (depend-
ing on the current switching state of the respective component).
Change switch state. (e.g. with a wire bridge at the digital input)
The display toggles between '0' and '1'.
Press the SET key again: The display shows the current parame-
ter name again.
Range
Def.
o.21 Test digital input
0: Input not connected
1: Input wired (bridged)
0 .. 1
- - -
Code 212
Code 345
Working level
Cooling parameter 1
C parameter
Cooling parameter 2
P parameter
Hardware configuration
A parameter
I/O test parameter
o. parameter