6. Setting of parameters
106082
– MRF-M2 -E - V0.7 - 23.04.2021
Page 27
to section 6.2: Level
“Cooling parameters 1” (C parameters)
Cooling time monitoring
Range
Default
C81 Monitoring of the max. compressor run time
A timer starts each time the compressor starts.
If the compressor run time exceeds the value
entered here, the fault message 'F20' appears
on the display.
Value '0' = function deactivated.
0 .. 999 min.
0
Sensor correction adjustment
(see also section 7.6)
Range
Default
c90 Display actual temperature sensor
c91 Sensor correction sensor
A correction can be applied to the value meas-
ured by the sensor. Then applies it cumulatively
throughout the entire measurement range.
10 .. 10 K
Software version
Range
Default
C98 Installed software version
The software version installed is shown to help
service technicians.
Button lock
Range
Default
C99 Button lock
The adjustment of the target temperatures in the
working level can be blocked by setting the but-
ton lock.
0: Buttons not locked
1: Buttons locked.
0 .. 1
0