Installation and operating instruction
Oil condensing boiler WTC-OB 18-B
6 Operation
83311002 1/2018-03 La
59-132
6.13 Chimney sweep
The function is used for flue gas measurement. During the chimney sweep function,
the appliance runs at maximum capacity.
Activate chimney sweep function
Turn dial knob.
Tool bar appears.
Set the selection cursor below the chimney sweep symbol.
Press [Enter]
The appliance starts according to the program sequence [ch. 3.3.5].
An
H
is indicated in the display during the preheating phase. The display then
shows the current supply temperature following flame formation. The chimney
sweep function remains activated for 25 minutes.
1
1
1
2
1
Flow temperature
2
Capacity [kW]
Deactivate chimney sweep function
Turn dial knob.
ESC
appears.
Press [ENTER].
Chimney sweep function is deactivated.
The standard display re-appears after approx. 90 seconds.