Installation and operating instruction
Oil condensing boiler WTC-OB 18-B
5 Installation
83311002 1/2018-03 La
27-132
Install siphon
Install siphon
1
, while pressing the termination well slightly downwards.
If there is another siphon downstream of the condensing boiler:
Remove cap
2
from the ventilation opening using a knife.
1
2
Install condensate hose
Place condensate hose in such a way that it is not possible for water bags to form
(siphon effect) and the condensate can drain away unimpeded.
Fit condensate hose to siphon, see installation examples.
If necessary fit condensate hose sleeve.
Run condensate hose to condensate outlet pipe.
Filling the siphon
Fill the siphon with water via the flue gas outlet or inspection opening, until water
flows from the condensate hose.
CAUTION
Damage to boiler due to the accumulation of condensate
An accumulation of condensate can cause faults or damage the appliance.
If there is another siphon downstream of the appliance:
Install a connection piece with breather opening between the two siphons.