Cause and rectification of faults
Most irregularities and faults of the boiler are recognised
by the WCM and shown on the display. The display
differentiates between faults (boiler lockout) and
warnings.
Faults
(crossed out flame signal flashes)
Proceed as follows with
faults
:
•
Note down the fault displayed (flashing)
•
Press reset key
Warning
With
warnings
the boiler does not lock out.
The warning is shown in the display and expires by
itself once the cause of the warning no longer exists.
Table of fault and warning message:
CODE Message Cause
Possible
fault/rectification
Temperatures
11
Fault
Boiler temperature
≥
105°C
• No water in boiler - top up water
• Air in boiler - vent boiler
• No boiler throughput - check function of pump,
clean water side of heat exchanger
12
Warning
Boiler temperature
≥
95°C
• No water in boiler - top up water
• Air in boiler - vent boiler
• No boiler throughput - check function of pump,
clean water side of heat exchanger
13
Fault
Flue gas temperature
≥
120°C
• Heat exchanger heavily soiled
14
Warning
Flow temperature
• Air in boiler - vent boiler
gradient too large
• No boiler throughput
• System pressure too low
15
Warning /
Temperature differential between
• Heat exchanger through flow insufficient
fault
)
boiler temp. and flue gas temp. too high
16
Warning
Flue gas temperature
≥
115°C
• Heat exchanger heavily soiled
18
Warning
Ratio STL/flow
• Heat exchanger through flow insufficient
1)
After 30 consecutive warnings the boiler goes to
lockout.