38
6
Limited
Code
Process value
display
Unit
System
I10
Operating phase (see also
➩
table operating phases Ch. 6.3.2)
I11
Load setting
[%]
I12
Damped external temperature of weather compensation
B1
[°C]
I13 Heat
demand
FS/EM heat circuit
[°C] or [%]
I14
SCOT
®
base value
[Point]
I15
Temperature setpoint remote control operation 4…20 mA
N1
[mA]
Actuators
I21
Start signal gas correcting element
[%]
I22
Set speed PWM pump
PWM pump
[%]
I23
Fan speed
[x10 RPM]
Sensors
I30
Flow temperature (safety temperature sensor)
[°C]
I31
Flue gas temperature
[°C]
I32
Ionisation signal (SCOT
®
actual value)
[Point]
I33
External temperature B1
B1
[°C]
I34
DHW temperature (versions -W/-C)
B3/-C
[°C]
I37
Throughput value (version -C)
-C
[l/min]
I38
Temperature calorifier sensor B10
P1/P2
[°C]
I39
Temperature calorifier B11
P2 / P3
[°C]
System info
I40
Daily switch cycle counter burner 0...999
I41
Daily operating hours counter burner 0...255
h
I42
Switch cycle counter burner
[x 1000]
I43
Operating hours counter burner
[h x 100]
I44
Software version (v = Version; r = Revision)
v.r
I45
Time since last service
[h x 10]
E
ES
SC
C
= exit menu
6.3.2 Info mode
Here, specific system values can be displayed.
By turning the dial knob, the individual operating status
values can be interrogated.
Each value can be assigned to the next list via a row
number.
➩
Entries in column “Limited display” show the relevant
configuration or the relevant features, for which the
value is displayed.
Resetting temporary information
☞
The daily counters I40, I41, the damped
external temperature I12 and the time since last
service I45 when displayed are reset by pressing the
key (approx. 2 seconds) .
Once I45 has been reset, the flashing spanner symbol
goes out.