Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
7 Commissioning
83300002 1/2019-02 La
47-128
Preset setting pressure
Only in conjunction with W-MF and gas connection pressure > 150 mbar
The pre-pressure must be set to approx. 90 mbar.
Set FRS pressure regulator, see additional sheet (print No. 835109xx).
Preset setting pressure determined at multifunction assembly.
De-energise pressure regulator (2" … DN 80)
Remove closing cap
1
and de-energise spring
2
.
1
2