Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
7 Commissioning
83300002 1/2019-02 La
57-128
Press [+] key.
Factory setting operating point P
1
(partial load) is displayed.
Press [Enter] and [L/A] simultaneously.
Factory setting fan speed (
100
%) is displayed.
Press [+] key to confirm factory setting.
Factory setting operating point P
0
(ignition position) is displayed.
Press [Enter] and [L/A] simultaneously.
Factory setting fan speed (
70
%) is displayed.
Press [+] key to confirm factory setting.
Combustion manager is preset.