Gas burner WG40…/1-A ZM-LN
7 Commissioning
83300002 1/2019-02 La
51-128
Press [+] key to confirm factory setting.
Factory setting operating point P
0
(ignition position) is displayed.
Press [+] key to confirm factory setting.
Combustion manager is preset.
2. Check sequence of operation
Open gas isolating valve.
Pressure in gas valve train increases.
Close isolating valve.
Plug in bridging plug No. 7 on combustion manager.
Burner starts.
Valve proving is carried out.
Check sequence of operation:
Valves open.
Gas pressure switch reacts.
Burner start is interrupted.
Burner does not detect a flame and goes to lockout.
Reset burner using the [ENTER] key.
Combustion manager drives to Standby.