Installation and operating instruction
Gas burner WG10…/0-D ZM-LN
9 Servicing
83300902 1/2019-02 La
66-112
9.2 Service plan
Components
Criteria / design lifespan
(1
Service procedure
Fan wheel
Soiling
Clean
Damage
Replace
Air duct
Soiling
Clean
Air damper
Soiling
Clean
Air pressure switch
Switch point
Check
250 000 burner starts or 10 years
(2
Replace
Ignition cable
Damage
Replace
Ignition electrode
Soiling
Clean
Damage/wear
Replace
Combustion Manager
250 000 burner starts or 10 years
(2
Replacement recommended
Ionisation cable
Damage
Replace
Ionisation electrode
Soiling
Clean
Damage/wear
Replace
Recommendation: at least every 2 years
Flame tube/diffuser
Soiling
Clean
Damage
Replace
Multifunction assembly
with valve testing system (valve
proving)
Fault identified
Replace
Multifunction assembly
without valve testing system
(valve proving)
Function / soundness
200 000 burner starts or 10 years
(2
Replace
Gas pressure regulator
Setting pressure
Check
Function / soundness
Replace
15 years
Replace
Gas pressure switch
Switch point
Check
50 000 burner starts or 10 years
(2
Replace
(1
The specified design lifespan applies for typical use in heating, hot water and steam systems as well as for thermal
process systems to EN 746.
(2
If a criterion is reached, carry out maintenance measures.