Installation and operating instruction
Gas burner WG10…/0-D ZM-LN
7 Commissioning
83300902 1/2019-02 La
49-112
Set diffuser
With dimension X = 0 mm the indicating bolt is flush with the cover of the nozzle
assembly.
Turn screw
1
, until dimension X equals the value determined.
1
X
7.1.8 Preset gas and air pressure switch
The presetting of the pressure switches is only valid during commissioning. Once
commissioning has been completed the pressure switches must be set correctly
[ch. 7.3].
Air pressure switch
approx. 2 mbar
Low gas pressure switch/valve proving gas pressure
switch
12 mbar
High gas pressure switch (optional)
approx. twice control pres-
sure