A more detailed description of the functions can be found in the
individual function descriptions.
M.
Function „Switching, Dimming, Shutter, Send value,
Scene“
If an input function of a channel is selected, the following param-
eters are displayed:
Type
The mode of operation of the contact connected to the input
channel can be configured here:
-
Normally open contact
-
Normally closed contact
Lock function
With this parameter the lock function can be enabled. If this
functionality is activated, the associated group objects as well as
the parameter page “Input B1: Lock function” are displayed for
further configuration. If the lock has been activated via the group
object, no telegrams are triggered by state changes of the con-
nected contact.
Group Object
Type KNX
Size
Direction
GO 26 Input B1: Lock - Activate
1.001
1 Bit
From KNX
N.
Input B1: Lock function
Polarity of object
This parameter defines, if the lock should be activated by receiv-
ing a 1 or by receiving a 0.
The following options are selectable:
-
Lock active on 1
-
Lock active on 0
Behavior of (…) on start
The telegram can be configured here, which is sent when the
lock is activated.
Behavior of (…) at end
The telegram can be configured here, which is sent when the
lock is deactivated.
O.
Function „Impulse counter“
If the impulse counter function is selected, further parameters
are displayed in the general settings of the input channel. Here,
the general settings of the impulse counter are made, a scaled
counter and/or counter of the rate of change must also be se-
lected.
Input signal
Here it can be selected whether DC or alternating voltage is
applied to the binary input.
Count on
This parameter can be used to determine whether the value of
the counter is increased at the rising or falling edge at the input
Scaled counter (e.g. [kWh])
Here, the scaled counter can be activated, the parameter page
"Scaled counter" is displayed when activated.
Rate of change (e.g. [kW], [m/s], [km/h])
The counter for a rate of change can be activated here. If acti-
vated, the "Rate of change" parameter page is displayed.
P.
Input B1: Switching
If the switching function is selected, up to 2 binary switching
telegrams can be sent via the following objects:
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Output a
– Switch
1.001
1 Bit
To KNX
GO 22 Input B1: Output b
– Switch
1.001
1 Bit
To KNX
Output b is only visible when activated by parameter.
User control
The parameter
“User control” determines whether telegrams are
sent when the input is changed (e.g. key switches) or when the
input is operated short/long (e.g. switching/dimming switches).