Weinzierl KNX IO 511 Operation And Installation Manual Download Page 11

©

2019 WEINZIERL ENGINEERING GmbH 

Page 11/15

 

Send condition 

This parameter can be used to determine how the current coun-
ter value is to be sent: 

On read 

No independent sending of the counter value by the 
device. To read the counter value, the read-flag of the 
group object has to be set. 

On change 

An additional parameter is displayed to select the min-
imal delta from the last sent value for sending a new 
counter value 

Cyclically 

An additional parameter is displayed to configure the 
sending frequency of the counter variable. 

On change and cyclically 

Both sending conditions are active. 

If the counter is locked by the object, also cyclic sending is 
stopped. 

Monitoring limit value 

When limit monitoring is activated, the following object is dis-
played: 

Group Object 

Type KNX 

Size 

Direction 

GO 22 Input B1: Counter threshold 

– State 

1.002 

1 Bit

To KNX 

 

When limit monitoring is activated, the following parameters are 
displayed: 

Limit value 

Here you can edit the checked limit value. The data-
point type is the same as the counter value. 

Behavior on reaching limit value (object) 

Here it is possible to determine whether a 0 or a 1 is 
sent via the object 

“Counter threshold – State” when 

the limit value is reached. 

Behavior on reaching limit value (counter) 

In addition to the limit value itself, it is possible to de-
termine the behavior of the counter when the limit val-
ue is reached: 

Counter continue 

Counter value continues increasing on ever 
pulse 

-  

Counter reset and continue 

Counter value is reset to 0 and continues in-
creasing on ever pulse 

Counter stop 

Counter value stays on limit value and must 
be reset by object 

Send on device restart 

It can be determined with this parameter whether the counter 
value should be sent when the device is restarted. 

Reset via object 

If this function is activated, the following object appears: 

Group Object 

Type KNX 

Size 

Direction 

GO 25 Input B1: Reset 

– Trigger 

1.017 

1 Bit

From KNX 

 

When a telegram is received via this object, the current count 
values are reset to 0. 

Reset after ETS download 

If this parameter is activated, the counter values are reset to 0 
after device reset (e.g. after ETS download), otherwise they are 
retained. 

Lock function 

The lock function can be activated or deactivated here. If this 
functionality is activated, the following group object appears, as 
well as the parameter page "Lock function" for detailed configu-
ration.  

Group Object 

Type KNX 

Size 

Direction 

GO 26 Input B1: Lock 

– Activate 

1.001 

1 Bit

From KNX 

If the lock has been activated via the group object, state changes 
at the input do not cause an increase of the counter variable.  

V. 

Input B1: Lock function 

 

Polarity of object 

This parameter can be used to determine how the lock is to be 
activated, either by receiving a 1 or a 0. The corresponding 
telegram disables the lock again. 

Behavior on start of lock 

With this parameter the behavior of the counter can be config-
ured when the lock is activated: 

Counter stop 

Counter stop and reset 

Behavior on end of lock  

With this parameter the behavior of the counter can be config-
ured when the lock is deactivated: 

Counter continue 

Counter reset and continue 

 

Summary of Contents for KNX IO 511

Page 1: ...and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is successful ly powered by the KNX bus By pressing button A long the manual operation mode will be entered for channel A This is indicated by cyclic single flashing of LED Ch M in orange The actuator channel A can be switched on with button On and switched off with button Off The manual op...

Page 2: ... settings It is possible to reset the device to its factory settings Disconnect the KNX Bus connector from device Press the KNX programming button and keep it pressed down Reconnect the KNX Bus connector of device Keep the KNX programming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 4 Wiring sch...

Page 3: ... expiry of the time limit or manually the last state of the outputs remains until a new switching telegram is received again The following options are selectable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit Heartbeat Cyclic sending of values to the KNX Bus to indicate that the device is operational For the Cycle tim...

Page 4: ...r to prevent unmeant switching Nevertheless the individual lamps can controlled by use of the priority object without cancel ing the lock F Lock function Polarity of object This parameter defines if the lock should be activated by receiv ing a 1 or by receiving a 0 The following options are selectable Lock active on 1 Lock active on 0 Behavior on start This parameter configures which state the out...

Page 5: ...e The duration of the switch off delay is configured in this parame ter Input 1 0 Output 1 T 0 Retriggerable If these parameters are activated the respective delay time is restarted upon receipt of the corresponding switching signal Function Staircase function If the staircase function is selected on the parameter page Ac tuator 1 General a group object for the staircase function appears in additi...

Page 6: ...control value is expressed in percent and defines the period during which the output is switched on in one cycle Example Cyclic time 10 Min Maximum control value PWM 80 Maximal output state ON 8 min OFF 2 min Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enab...

Page 7: ... the lock is activated this value can be set with this parameter L Input B1 General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group objects are named Input with the channel number which ...

Page 8: ...telegram can be configured here which is sent when the lock is deactivated O Function Impulse counter If the impulse counter function is selected further parameters are displayed in the general settings of the input channel Here the general settings of the impulse counter are made a scaled counter and or counter of the rate of change must also be se lected Input signal Here it can be selected whet...

Page 9: ...it To KNX Shutter function The Shutter function parameter determines whether only one shutter direction or 1 button control is to be used Up Step Stop Down Step Stop Toggle direction User control The parameter User control determines the sending of tele grams on short and long button press Long Drive Short Step Stop Long button press Drive command via object 21 Short button press Stop step command...

Page 10: ... button press the configured delay time is started Starting with the first scene position the next scene position of the list is sent with each short button press after the last scene position has been sent the list starts again from the beginning After the delay time has expired the list starts again at the first scene position on the next short button press When the lock function is used the sce...

Page 11: ...t and continue Counter value is reset to 0 and continues in creasing on ever pulse Counter stop Counter value stays on limit value and must be reset by object Send on device restart It can be determined with this parameter whether the counter value should be sent when the device is restarted Reset via object If this function is activated the following object appears Group Object Type KNX Size Dire...

Page 12: ...ameter is displayed to select the min imal delta from the last sent value for sending a new counter value Cyclically An additional parameter is displayed to configure the sending frequency of the counter variable On change and cyclically Both sending conditions are active Monitoring limit value When limit monitoring is activated the following object is dis played Group Object Type KNX Size Directi...

Page 13: ... as the input of the next function Y Function 1 16 Timer Function name 10 Characters The function name can be chosen freely The name is visible in the group object entry in the ETS soft ware This makes it easier to work with the associated group objects because the given name is displayed there as a label Timer type Switch on delay A timer that switches ON after duration defined in Delay time s pa...

Page 14: ... type AND gate The output is triggered on 1 if both inputs are switched on 1 Gate type OR gate The output is triggered on 1 if one or both inputs are switched on 1 Gate type XOR gate The output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are...

Page 15: ...idered The device is a permanently connected equipment A readily accessible disconnect device shall be in corporated external to the equipment The installation requires a 16 A fuse for external overcurrent protection The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 511 ets4 Datasheet www weinzierl de en products 511 datasheet CE Declaration www ...

Reviews: