General settings:
Device name (30 Characters)
An arbitrary name can be assigned for the KNX IO 511 (1O2I).
The device name should be meaningful, e.g.
„Living Room“. This
helps the clarity of the ETS project.
Send delay after bus power return
A send delay of telegrams after the return of the bus voltage can
be set via this parameter. In this case, telegrams from the device
are sent to the KNX bus in a delayed manner by the set time.
This results in a reduction of the bus load at a bus power return.
Other functions such as receiving telegrams of switching opera-
tions of the actuator are not affected by this parameter.
Prog. mode on device front
In addition to the normal programming button
❸
the device
allows activating the programming mode on the device front
without opening the switchboard cover. The programming mode
can be activated and deactivated via pressing simultaneously
both buttons
❼
and
❽
.
This feature can be enabled and disabled via the parameter
“Prog. mode on device front”. The recessed programming button
❸
(next to the Programming LED
❷
) is always enabled and
not influenced by this parameter.
Manual operation on device
This parameter is used to configure the manual operation on the
device. The manual operation mode can be disabled or activated
(with or without time limitation). The time limit defines the dura-
tion until the automatic return from the manual operation mode
back into the normal operating mode.
The device is in normal operating mode when the manual control
is not active. In the manual operating mode, received switching
telegrams are ignored. When the manual operation mode is
terminated (after expiry of the time limit or manually), the last
state of the outputs remains, until a new switching telegram is
received again.
The following options are selectable:
-
Disabled
-
Enabled with time limit 1 min
-
Enabled with time limit 10 min
-
Enabled with time limit 30 min
-
Enabled without time limit
Heartbeat
Cyclic sending of values to the KNX-Bus, to indicate that the
device is operational. For the
Cycle time
values between 1 min
and 24h are selectable.
Group Object
Type KNX
Size
Direction
GO 1 Heartbeat - Trigger
1.001
1 Bit
To KNX
Long button press after
The time for detection of a long button press can be set here,
this time is valid for all input channels.
E.
Actuator 1: General:
Name (30 Characters)
An arbitrary name can be assigned for the channel. However,
this should be clear and meaningful, this makes it easier to work
with the associated group objects, because the given name is
displayed there as a label. If no name is assigned, the group
objects are named “Actuator A: …”.
Function
This parameter defines the functionality of the actuator.
The following options are selectable:
-
Disabled
-
Universal output
-
On/Off delay
-
Staircase function
-
Valve actuator (PWM for thermal servo)
A more detailed description of the functions can be found in the
individual function descriptions under Func
tion (…).
If the
actuator is not “Disabled”, the following parameters are
displayed:
Behavior on bus power failure
The behavior which is held at the output during the bus power
failure can be configured here.
The following options are selectable:
-
No reaction
-
Switch on
-
Switch off
Behavior after bus power return
Here the behavior of the output after bus power return can be
configured. This behavior will be set after every device restart
(e.g. also on restart after ETS download).
The following options are selectable:
-
No reaction
-
Switch on
-
Switch off
-
State like before bus power failure