Weinzierl KNX IO 511 Operation And Installation Manual Download Page 3

©

2019 WEINZIERL ENGINEERING GmbH 

Page 3/15

 

General settings: 

 

 

Device name (30 Characters) 

An arbitrary name can be assigned for the KNX IO 511 (1O2I). 
The device name should be meaningful, e.g. 

„Living Room“. This 

helps the clarity of the ETS project. 

Send delay after bus power return 

A send delay of telegrams after the return of the bus voltage can 
be set via this parameter. In this case, telegrams from the device 
are sent to the KNX bus in a delayed manner by the set time. 
This results in a reduction of the bus load at a bus power return. 
Other functions such as receiving telegrams of switching opera-
tions of the actuator are not affected by this parameter. 

Prog. mode on device front 

In addition to the normal programming button 

 the device 

allows activating the programming mode on the device front 
without opening the switchboard cover. The programming mode 
can be activated and deactivated via pressing simultaneously 
both buttons 

 and 

.  

This feature can be enabled and disabled via the parameter 
“Prog. mode on device front”. The recessed programming button 

 (next to the Programming LED 

) is always enabled and 

not influenced by this parameter.  

Manual operation on device 

This parameter is used to configure the manual operation on the 
device. The manual operation mode can be disabled or activated 
(with or without time limitation). The time limit defines the dura-
tion until the automatic return from the manual operation mode 
back into the normal operating mode. 

The device is in normal operating mode when the manual control 
is not active. In the manual operating mode, received switching 
telegrams are ignored. When the manual operation mode is 
terminated (after expiry of the time limit or manually), the last 
state of the outputs remains, until a new switching telegram is 
received again. 

The following options are selectable: 

Disabled 

Enabled with time limit 1 min 

Enabled with time limit 10 min 

Enabled with time limit 30 min 

Enabled without time limit 

Heartbeat 

Cyclic sending of values to the KNX-Bus, to indicate that the 
device is operational. For the 

Cycle time

 values between 1 min 

and 24h are selectable. 

Group Object 

Type KNX 

Size 

Direction 

GO 1 Heartbeat - Trigger 

1.001 

1 Bit 

To KNX 

 
 

Long button press after 

The time for detection of a long button press can be set here, 
this time is valid for all input channels. 

E. 

Actuator 1: General:

 

 

 

 

Name (30 Characters) 

An arbitrary name can be assigned for the channel. However, 
this should be clear and meaningful, this makes it easier to work 
with the associated group objects, because the given name is 
displayed there as a label. If no name is assigned, the group 
objects are named “Actuator A: …”. 

Function 

This parameter defines the functionality of the actuator.  

The following options are selectable: 

Disabled 

Universal output 

On/Off delay 

Staircase function 

Valve actuator (PWM for thermal servo) 

A more detailed description of the functions can be found in the 
individual function descriptions under Func

tion (…). 

If the 

actuator is not “Disabled”, the following parameters are 

displayed: 

Behavior on bus power failure 

The behavior which is held at the output during the bus power 
failure can be configured here.  

The following options are selectable: 

No reaction 

Switch on 

Switch off 

 
Behavior after bus power return 

Here the behavior of the output after bus power return can be 
configured. This behavior will be set after every device restart 
(e.g. also on restart after ETS download). 

The following options are selectable: 

No reaction 

Switch on 

Switch off 

State like before bus power failure 

Summary of Contents for KNX IO 511

Page 1: ...and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is successful ly powered by the KNX bus By pressing button A long the manual operation mode will be entered for channel A This is indicated by cyclic single flashing of LED Ch M in orange The actuator channel A can be switched on with button On and switched off with button Off The manual op...

Page 2: ... settings It is possible to reset the device to its factory settings Disconnect the KNX Bus connector from device Press the KNX programming button and keep it pressed down Reconnect the KNX Bus connector of device Keep the KNX programming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 4 Wiring sch...

Page 3: ... expiry of the time limit or manually the last state of the outputs remains until a new switching telegram is received again The following options are selectable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit Heartbeat Cyclic sending of values to the KNX Bus to indicate that the device is operational For the Cycle tim...

Page 4: ...r to prevent unmeant switching Nevertheless the individual lamps can controlled by use of the priority object without cancel ing the lock F Lock function Polarity of object This parameter defines if the lock should be activated by receiv ing a 1 or by receiving a 0 The following options are selectable Lock active on 1 Lock active on 0 Behavior on start This parameter configures which state the out...

Page 5: ...e The duration of the switch off delay is configured in this parame ter Input 1 0 Output 1 T 0 Retriggerable If these parameters are activated the respective delay time is restarted upon receipt of the corresponding switching signal Function Staircase function If the staircase function is selected on the parameter page Ac tuator 1 General a group object for the staircase function appears in additi...

Page 6: ...control value is expressed in percent and defines the period during which the output is switched on in one cycle Example Cyclic time 10 Min Maximum control value PWM 80 Maximal output state ON 8 min OFF 2 min Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enab...

Page 7: ... the lock is activated this value can be set with this parameter L Input B1 General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group objects are named Input with the channel number which ...

Page 8: ...telegram can be configured here which is sent when the lock is deactivated O Function Impulse counter If the impulse counter function is selected further parameters are displayed in the general settings of the input channel Here the general settings of the impulse counter are made a scaled counter and or counter of the rate of change must also be se lected Input signal Here it can be selected whet...

Page 9: ...it To KNX Shutter function The Shutter function parameter determines whether only one shutter direction or 1 button control is to be used Up Step Stop Down Step Stop Toggle direction User control The parameter User control determines the sending of tele grams on short and long button press Long Drive Short Step Stop Long button press Drive command via object 21 Short button press Stop step command...

Page 10: ... button press the configured delay time is started Starting with the first scene position the next scene position of the list is sent with each short button press after the last scene position has been sent the list starts again from the beginning After the delay time has expired the list starts again at the first scene position on the next short button press When the lock function is used the sce...

Page 11: ...t and continue Counter value is reset to 0 and continues in creasing on ever pulse Counter stop Counter value stays on limit value and must be reset by object Send on device restart It can be determined with this parameter whether the counter value should be sent when the device is restarted Reset via object If this function is activated the following object appears Group Object Type KNX Size Dire...

Page 12: ...ameter is displayed to select the min imal delta from the last sent value for sending a new counter value Cyclically An additional parameter is displayed to configure the sending frequency of the counter variable On change and cyclically Both sending conditions are active Monitoring limit value When limit monitoring is activated the following object is dis played Group Object Type KNX Size Directi...

Page 13: ... as the input of the next function Y Function 1 16 Timer Function name 10 Characters The function name can be chosen freely The name is visible in the group object entry in the ETS soft ware This makes it easier to work with the associated group objects because the given name is displayed there as a label Timer type Switch on delay A timer that switches ON after duration defined in Delay time s pa...

Page 14: ... type AND gate The output is triggered on 1 if both inputs are switched on 1 Gate type OR gate The output is triggered on 1 if one or both inputs are switched on 1 Gate type XOR gate The output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are...

Page 15: ...idered The device is a permanently connected equipment A readily accessible disconnect device shall be in corporated external to the equipment The installation requires a 16 A fuse for external overcurrent protection The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 511 ets4 Datasheet www weinzierl de en products 511 datasheet CE Declaration www ...

Reviews: