Weinzierl KNX IO 511 Operation And Installation Manual Download Page 6

©

2019 WEINZIERL ENGINEERING GmbH 

Page 6/15

 

Time for warning before switch off 

The time between pre-warning and deactivation is configured, or 
the pre-warning is deactivated with this parameter. If the pre-
warning time is longer than the actual follow-up time, no pre-
warning is carried out. 

Time of interrupt 

The pre-warning is indicated by a brief interruption (switch off -> 
switch on). The duration of this interrupt is configured in this 
parameter. 

Note: LED lamps often have a long follow-up time, in which the 
lamp still lights even though it is already switched off. With such 
lamps longer interrupt times must be set to generate a "visible" 
interruption. 

 
Function (Valve actuator) 

The function valve actuator is foreseen to control thermoelectric 
valve drives which are used for floor heating but also for radia-
tors. It maps the continuous position (0% - 100%) to an ongoing 
On/Off sequence called PWM (pulse width modulation) signal. 

If the valve actuator is selected on the parameter page "Actuator 
1: General", a group object for the valve actuator appears in-
stead of the normal switching object. This allows the current 
PWM at the output to be set via KNX (0% - 100%). An additional 
parameter page "Actuator 1: Valve actuator" appears for the 
configuration of the valve actuator. 

The received control value is saved automatically by the device, 
to continue faultless after a possible bus power loss. 

Group Object 

Type KNX 

Size 

Direction 

GO 14 Actuator 1: Valve actuator (PWM) 
– Control value 

5.001 

1 Byte 

From KNX 

 

J. 

Valve actuator: 

 

 

 

Cyclic time (PWM) 

The cyclic time of the PWM, which is used to control a servo 
drive, is configured with this parameter. One cycle involves a 
time range in which the output is switched on and one in which 
the output is switched off. The cyclic time corresponds to the 
period between two rising edges (state change at the output 
from OFF to ON). The longer the flow of the heating circuit (tube 
/ pipe length), the higher the cyclic time should be set. 

Note: Typical thermal servo require several minutes for a 100% 
valve change. 

Maximum control value (PWM) 

This parameter can be used to limit the maximum control value. 
The control value is expressed in percent and defines the period 
during which the output is switched on in one cycle. 

Example: 
Cyclic time = 10 Min. 
Maximum control value (PWM) = 80 % 
Maximal output state = ON - 8 min / OFF - 2 min 

Stuck protection 

With the stuck protection, it is intended to prevent the valve from 
being damaged by corrosion or calcification, that it can no longer 
be moved. In case stuck protection is enabled, this is only trig-
gered if the value is permanently 0 % or 100 %. On every other 
control value the servo already moves, so there is no need for a 
stuck protection. 

Control value 0%  

 Open servo for the set time 

Control value 100% 

 Close servo for the set time 

In case the valve is not allowed to open, the stuck protection 
must be disabled. 

Execution time 

If the stuck protection is activated, this parameter is used to set 
the duration of the state change. 

Monitoring interval 

If the stuck protection is activated, this parameter sets the moni-
toring interval. If the state of the output remains unchanged for 
this time, the lock protection is triggered. 

Protection on missing control value 

This parameter enables the protection function on missing con-
trol value telegrams. This is necessary in order to prevent un-
wanted and uncontrolled overheating or cooling down of the 
room, when the control value is missing. 

Protection takes effect, as soon as no telegrams are received 
from the controller over a longer period of time. As soon as this 
extended telegram pause has occurred, it can be assumed that 
the corresponding controller has failed or the connection be-
tween the controller and the valve actuator has been interrupted. 

Protection control value (PWM) 

If the protection on missing control value is enabled, this pa-
rameter sets a protection control value. This configured PWM 
value will set the output, if the protection is active. 

As soon as telegrams from the controller are received again, the 
protection control value (PWM) is overwritten by the received 
value. The protection does not react again, until the waiting time 
in the set monitoring interval is exceeded between individual 
telegrams. 

Monitoring interval 

If the protection on missing control value is enabled, this pa-
rameter sets the monitoring interval. If no further telegram is 
received by the device during this time, the protection function 
takes effect. 

 

 

Summary of Contents for KNX IO 511

Page 1: ...and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is successful ly powered by the KNX bus By pressing button A long the manual operation mode will be entered for channel A This is indicated by cyclic single flashing of LED Ch M in orange The actuator channel A can be switched on with button On and switched off with button Off The manual op...

Page 2: ... settings It is possible to reset the device to its factory settings Disconnect the KNX Bus connector from device Press the KNX programming button and keep it pressed down Reconnect the KNX Bus connector of device Keep the KNX programming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 4 Wiring sch...

Page 3: ... expiry of the time limit or manually the last state of the outputs remains until a new switching telegram is received again The following options are selectable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit Heartbeat Cyclic sending of values to the KNX Bus to indicate that the device is operational For the Cycle tim...

Page 4: ...r to prevent unmeant switching Nevertheless the individual lamps can controlled by use of the priority object without cancel ing the lock F Lock function Polarity of object This parameter defines if the lock should be activated by receiv ing a 1 or by receiving a 0 The following options are selectable Lock active on 1 Lock active on 0 Behavior on start This parameter configures which state the out...

Page 5: ...e The duration of the switch off delay is configured in this parame ter Input 1 0 Output 1 T 0 Retriggerable If these parameters are activated the respective delay time is restarted upon receipt of the corresponding switching signal Function Staircase function If the staircase function is selected on the parameter page Ac tuator 1 General a group object for the staircase function appears in additi...

Page 6: ...control value is expressed in percent and defines the period during which the output is switched on in one cycle Example Cyclic time 10 Min Maximum control value PWM 80 Maximal output state ON 8 min OFF 2 min Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enab...

Page 7: ... the lock is activated this value can be set with this parameter L Input B1 General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group objects are named Input with the channel number which ...

Page 8: ...telegram can be configured here which is sent when the lock is deactivated O Function Impulse counter If the impulse counter function is selected further parameters are displayed in the general settings of the input channel Here the general settings of the impulse counter are made a scaled counter and or counter of the rate of change must also be se lected Input signal Here it can be selected whet...

Page 9: ...it To KNX Shutter function The Shutter function parameter determines whether only one shutter direction or 1 button control is to be used Up Step Stop Down Step Stop Toggle direction User control The parameter User control determines the sending of tele grams on short and long button press Long Drive Short Step Stop Long button press Drive command via object 21 Short button press Stop step command...

Page 10: ... button press the configured delay time is started Starting with the first scene position the next scene position of the list is sent with each short button press after the last scene position has been sent the list starts again from the beginning After the delay time has expired the list starts again at the first scene position on the next short button press When the lock function is used the sce...

Page 11: ...t and continue Counter value is reset to 0 and continues in creasing on ever pulse Counter stop Counter value stays on limit value and must be reset by object Send on device restart It can be determined with this parameter whether the counter value should be sent when the device is restarted Reset via object If this function is activated the following object appears Group Object Type KNX Size Dire...

Page 12: ...ameter is displayed to select the min imal delta from the last sent value for sending a new counter value Cyclically An additional parameter is displayed to configure the sending frequency of the counter variable On change and cyclically Both sending conditions are active Monitoring limit value When limit monitoring is activated the following object is dis played Group Object Type KNX Size Directi...

Page 13: ... as the input of the next function Y Function 1 16 Timer Function name 10 Characters The function name can be chosen freely The name is visible in the group object entry in the ETS soft ware This makes it easier to work with the associated group objects because the given name is displayed there as a label Timer type Switch on delay A timer that switches ON after duration defined in Delay time s pa...

Page 14: ... type AND gate The output is triggered on 1 if both inputs are switched on 1 Gate type OR gate The output is triggered on 1 if one or both inputs are switched on 1 Gate type XOR gate The output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are...

Page 15: ...idered The device is a permanently connected equipment A readily accessible disconnect device shall be in corporated external to the equipment The installation requires a 16 A fuse for external overcurrent protection The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 511 ets4 Datasheet www weinzierl de en products 511 datasheet CE Declaration www ...