2019 WEINZIERL ENGINEERING GmbH
Page 10/15
-
14 byte - ASCII string
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send ASCII string (14
byte)
– Set value
16.000
14
Byte
To KNX
-
Shutter
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Send blind position
– Set
position
5.001
1 Byte
To KNX
GO 22 Input B1: Send slat position
– Set
position
5.001
1 Byte
To KNX
A field for entering the values to be sent is displayed, as well as
the objects appropriate to the selected type.
If the shutter is selected as the value to be sent, height is sent on
button press, lamella is sent on releasing the button, if the re-
spective value is used.
T.
Input B1: Scene
On selection of Scene function the following object is visible:
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Scene
– Activ./Lrn.
18.001
1 Byte
To KNX
Scene position 1 - 8
For each position, scene 1
– 64 can be activated.
If only one scene position is activated, it is sent on short button
press.
If several scene positions are used, the activated positions are
switched through with each short button press.
Reset scene position
The behavior for selection and transmission of the scene posi-
tions can be determined via the parameter "Reset scene posi-
tion":
-
Never
Starting with the first scene position, the next scene
position of the list is sent with each short button press,
after the last scene position has been sent, the list
starts again from the beginning.
-
After execution
Beginning with the first scene position, each short but-
ton press switches the scene position by one position
within the execution delay, at the end of the execution
delay, the current scene position is sent
-
5 Sec. - 10 Min.
On each button press the configured delay time is
started.
Starting with the first scene position, the next scene
position of the list is sent with each short button press,
after the last scene position has been sent, the list
starts again from the beginning.
After the delay time has expired, the list starts again at
the first scene position on the next short button press.
When the lock function is used, the scene position is always
reset when unlocking.
Condition on long/very long button press
It is also possible to select how a long and very long button
press is to be treated:
-
No reaction
-
Save last scene
A telegram for "save scene" with the last sent scene is
triggered.
-
Send scene
The scene configured in the appearing parameter is
sent.
-
Reset position
This function is used to override the behavior as set in
the "Reset scene position" parameter.
The duration of time for detecting a very long button press is
twice the time for detecting a long button press, as it is parame-
terized in the general settings.
U.
Input B1: Scaled counter
This counter can be used to count values on input impulses,
where an integer value or a floating-point value can be selected
as a counter variable. With this function, e.g. Electrical energy
can be counted directly and sent to the bus via an object.
Scaling factor (Value per pulse)
Here, a floating-point value is to be entered. It determines the
value by which the counter value is increased per pulse.
Datapoint type
The datapoint type of output object of the counter variable can
be selected here:
-
Integer (32 Bit)
– DPT 13
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Counter
– Value
13.013
4 Byte
To KNX
-
Float (16 Bit)
– DPT 9
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Counter
– Value
9.024
2 Byte
To KNX
-
Float (32 Bit)
– DPT 14
Group Object
Type KNX
Size
Direction
GO 21 Input B1: Counter
– Value
14.056
4 Byte
To KNX