background image

 

© 2021 W einzierl Engineering GmbH

 

Seite 4/16

 

 

1.3  Coupler 

– Function 

 

KNX RF/TP Coupler 673 secure as line coupler 

The physical address of the KNX RF/TP Coupler 673 secure corresponds to the form x.y.0 (x, y: 
1..15). Thus the device functions as a line coupler.

 

 

The unit functions as a coupler only if its physical address is of the form x.y.0. 

 

The KNX RF/TP Coupler 673 secure has a filter table and thus helps to reduce the bus load. The filter 
table supports the extended group address range (main groups 0..31) and is automatically generated 
by the ETS. 

 

KNX RF/TP Coupler 673 secure as wireless extension of a KNX line. 

 

 

Summary of Contents for 5188

Page 1: ...NX RF TP Coupler KNX Data Security KNX RF TP Coupler 673 secure Operation and installation manual Art 5188 KNX RF TP Coupler 673 secure Weinzierl Engineering GmbH Achatz 3 DE 84508 Burgkirchen Alz Tel 49 0 8677 91 636 0 info weinzierl de www weinzierl de ...

Page 2: ...evice 3 1 2 KNX Data Security for group telegrams 3 1 3 Coupler Function 4 2 Installation and commissioning 5 2 1 KNX Programming mode 5 2 2 Status display 5 2 3 Manual control TP 6 2 4 Manual control RF 6 3 Factory setting 6 3 1 Reset to factory settings 6 4 ETS Database 7 4 1 ETS Parameter dialog 10 ...

Page 3: ...installation KNX Data Security describes the encryption on telegram level This means that the telegrams are encrypted both on the twisted pair bus and via radio 1 1 KNX Data Security for the device The KNX RF TP Coupler 673 secure supports KNX Data Security to protect the device against unauthorised access from the KNX bus If the KNX RF TP coupler is programmed via the KNX bus this is done with en...

Page 4: ...1 15 Thus the device functions as a line coupler The unit functions as a coupler only if its physical address is of the form x y 0 The KNX RF TP Coupler 673 secure has a filter table and thus helps to reduce the bus load The filter table supports the extended group address range main groups 0 31 and is automatically generated by the ETS KNX RF TP Coupler 673 secure as wireless extension of a KNX l...

Page 5: ...pler 673 secure has the following controls and displays The device is only supplied via the KNX bus 2 1 KNX Programming mode The KNX programming mode is switched on or off via the KNX programming button P When the programming mode is active the programming LED lights up red When delivered the coupler has the individual Address 15 15 0 2 2 Status display The status LED lights up green when KNX bus ...

Page 6: ...the LEDs 5 and 6 Briefly pressing the B button enables disables the Routing of the individual addressed telegrams the system broadcast telegrams This is indicated by the LEDs 7 and 8 A long press on button A or button B terminates manual operation Manual control can be locked in the ETS database 3 Factory setting The following configuration is preset at the factory Physical address of the device 1...

Page 7: ...ssword This password protects the ETS project against unauthorized access This password is not a key that is used for KNX communication Entering the password can be bypassed with Cancel but this is not recommended for security reasons Without entering a password any security features cannot be used within the project For each device supporting KNX Security ETS requires a device certificate This ce...

Page 8: ... new key which is created for each device individually This prevents persons or devices that might know the initial key from accessing the device The initial key is only reactivated after a master reset The serial number in the certificate enables the ETS to assign the correct key to a device during a download By selecting the KNX RF TP Coupler 673 secure in the tree structure of the Topology View...

Page 9: ...adio line with the KNX RF TP Coupler 673 secure in the tree structure of the topology view of the ETS project the property dialog of the line appears on the right hand side of the ETS window In the tab Settings the domain address of the radio line can be changed ...

Page 10: ...wing parameters can be set with the ETS Description General information about the device is displayed here General Settings Device name 30 characters Any name for the KNX RF TP Coupler 673 secure can be assigned here The device name should be meaningful e g RF coupler ground floor ...

Page 11: ...egrams are forwarded to the RF line regardless of the filter table This setting should only be used for test purposes Filter The filter table is used to decide whether the received group telegram is to be forwarded to the RF line Individual addressed telegrams Block No physically addressed telegram is forwarded to the RF line Route All physically addressed telegrams are forwarded to the RF line Th...

Page 12: ...rwarded to the RF line Acknowledge ACK of group telegrams Always For received group telegrams from the TP line always send an acknowledge If routed For received group telegrams from the TP line an acknowledge is sent only when telegram is forwarded to the RF line Acknowledge ACK of individual telegrams Always For received individual addressed telegrams from the TP line an acknowledge is always sen...

Page 13: ...urposes Filter The destination address is used to check whether the received individual addressed telegram is forwarded to the TP line System broadcast telegrams Block No received System Broadcast telegram is forwarded to the TP line Route All received System Broadcast telegrams are forwarded to the TP line Broadcast telegrams Block No received broadcast telegram is forwarded to the TP line Route ...

Page 14: ...of individual addressed telegrams Disabled The forwarded individual addressed telegram will be not repeated in the TP line in case of an error Enabled The forwarded individual addressed telegram will be repeated up to three times in case of error Repetition of broadcast telegrams Disabled The forwarded broadcast telegram will be not repeated in the TP line in case of an error Enabled The forwarded...

Page 15: ... are included in the filter table for this purpose The contents of the filter table can be displayed via the preview Preview of the filter table The filter table can be extended by manually adding of the group addresses For this purpose Pass through Line Coupler must be activated in the properties window of the corresponding group address Properties window of a group address ...

Page 16: ...508 Burgkirchen Alz Germany www weinzierl de info weinzierl de 2021 11 09 WARNUNG The device may only be installed and put into operation by a certified electrician The applicable safety and accident prevention regulations contraceptive instructions must be complied with The device must not be opened When planning and installing electrical systems the relevant guidelines regulations and provisions...

Reviews: