Manual control on the device
Here the duration of the manual control mode is set. On termination, the system automatically returns
to normal operating mode.
The activated manual control can reduce the security of the installation.
Routing TP->RF
Group telegrams
Block:
No group telegram is forwarded to the RF line.
Route:
All group telegrams are forwarded to the RF line regardless of the filter table.
This setting should only be used for test purposes.
Filter:
The filter table is used to decide whether the received group telegram is to be
forwarded to
the RF line.
Individual addressed telegrams
Block:
No physically addressed telegram is forwarded to the RF line.
Route:
All physically addressed telegrams are forwarded to the RF line.
This setting should only be used for test purposes.
Filter:
The destination address is used to check whether the received individual addressed
telegram is forwarded to the RF line.