Boiler Manual
Control operation and setup
(continued)
&IGURE
SlimFit control settings available in BASIC MODE (see Advanced Manual for ADVANCED MODE settings)
&IGURE
System types available in BASIC MODE (each option shown with factory settings)
!VAILABLESETTINGSFROM#/.42!#4/2-%.5
"OILER3ETTINGS-ENU
0RIORITYMENU
!SSIGN)NPUTSMENU
s
Boiler Model
s
Inputs Assigned (non-selectable)
)NPUT44
s
Control Type
s
System Type
s
Priority 1, 2 or 3
s
High Altitude
s
Target Mod Sensor (non-selectable)
s
Source (TT1 or 0-10v)
s
Target Adjust (non-selectable)
s
AUX PUMP/OUTPUT
s
Manual Reset High Limit Temp
s
Supply Max
s
Off
s
WWSD Temp
s
Supply Min (not available for DHW) *
s
Adjust Outdoor
s
OD Reset Max (or Volts for Max) *
)NPUT44AND)NPUT44
s
Circulator Exercising
s
OD Reset Min (or Volts for Min) *
s
Priority 1, 2 or 3
s
Freeze Protect Circs
s
Boost Time *
s
AUX PUMP/OUTPUT
s
Reset Factory Default
s
Off
0RIORITYMENU
s
Inputs Assigned (non-selectable)
$IAGNOSTICSMENU
0RIORITYMENU
s
System Type
s
See Figure 67, page 73 for details.
s
Inputs Assigned (non-selectable)
s
Target Mod Sensor (non-selectable)
s
System Type
s
Target Adjust (non-selectable)
-AINTENANCE)NFOMENU
s
Target Mod Sensor (non-selectable)
s
Supply Max
s
See Figure 72, page 78 for details.
s
Target Adjust (non-selectable)
s
Supply Min (not available for DHW) *
s
Supply Max
s
OD Reset Max (or Volts for Max) *
3ET$ATEAND4IMEMENU
s
Supply Min (not available for DHW) *
s
OD Reset Min (or Volts for Min) *
s
See Figure 72, page 78 for details.
s
OD Reset Max (or Volts for Max) *
s
Boost Time *
s
OD Reset Min (or Volts for Min) *
* These items only appear in the menus if Target Adjust is active.
s
Boost Time *
3YSTEM4YPE
8-Character
Abbreviation
3-Character
Abbreviation
Supply Max
°F
OD Reset
Min °F
Supply
Min °F
OD Reset
Max °F
Run
Boiler Pump
Run AUX
PUMP/
OUTPUT
Fan-coil
FAN-COIL
FCL
180
0
140
70
YES
YES
Finned Tube Baseboard
FIN BASE
FTB
180
0
130
70
YES
YES
Cast Iron Baseboard
IRONBASE
CIB
180
0
120
70
YES
YES
Cast Iron Radiators
RADIATOR
CIR
180
0
120
70
YES
YES
Radiant - slab on grade
RAD SLAB
RSG
120
0
80
70
YES
YES
Radiant - thin slab
RAD SLAB
RTS
140
0
80
70
YES
YES
Radiant - below floor
(staple up)
RADFLOOR
RSU
160
0
90
70
YES
YES
Radiant - above floor
(sleeper system)
RADFLOOR
RAF
140
0
90
70
YES
YES
Domestic Hot Water
DOMESTIC
DHW
180
N/A
N/A
N/A
NO
NO
Custom (user defined)
XXXXXXXX
(user input)
first three of
user input
180
0
70
70
YES
YES