Part number 550-100-180/0917
29
SlimFit
®
Series 2
COMMERCIAL
CONDENSING
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
Venting/combustion air — options
&IGURE
SlimFit boiler venting and air piping — OPTIONS and PIPING LIMITS — The table below lists the acceptable
vent/air pipe terminations described in this manual.
USE ONLY the pipe materials listed in Figure 22, page 25 | See Figure 96, page 105 for part/kit numbers
Boiler vent and air connections:
Provide a vent pipe mfr’s
SlimFit VENT/AIR ADAPTER
at boiler vent connection and air connection (if used). See
Figure 96, page 105 for part/kit numbers
Provide vent pipe manufacturer’s reducer(s) as needed to meet vent/air pipe size used.
SlimF
it Model
P
ipe Siz
e
SIDEWALL
Direct Exhaust
VERTICAL
Direct Exhaust
SIDEWALL
Direct Vent
(vent and air out sidewall)
VERTICAL
Direct Vent
(vertical or sidewall air)
SF0061de
VENT
SF0062de
T
VENT
AIR
SF0062
T
o tio
See page 33
See page 35
See page 39
See page 41
Max/Min length, feet
(note 1)
Max/Min length, feet
(note 1)
Max/Min length, feet
(note 1)
Max/Min length, feet
(note 1)
Thickness for
wall/roof vent penetration;
Max: 8” Min: 0”
Thickness for
wall/roof vent penetration;
Max: 8” Min: 0”
Thickness for
wall/roof vent penetration;
Max: 8” Min: 0”
Thickness for
wall/roof vent penetration;
inches Max: 8” Min: 0”
SF1000
6”
100 max / 6 min
100 max / 6 min
100 max / 6 min
100 max / 6 min
8”
DO NOT USE 8”
DO NOT USE 8”
150 max / 6 min
150 max / 6 min
SF1500
6”
DO NOT USE 6”
DO NOT USE 6”
DO NOT USE 6”
DO NOT USE 6”
8”
100 max / 6 min
100 max / 6 min
100 max / 6 min
100 max / 6 min
SF2000
6”
DO NOT USE 6”
DO NOT USE 6”
DO NOT USE 6”
DO NOT USE 6”
8”
100 max / 6 min
100 max / 6 min
100 max / 6 min
100 max / 6 min
Note 1
REDUCE MAXIMUM VENT/AIR PIPE LENGTHS FOR ELBOWS
If the TOTAL number of elbows used in the vent and air piping and terminations is
more than two elbows in the vent
piping and one elbow
in the air piping,
REDUCE
the maximum lengths above by the following lengths for each additional
elbow (whether 45° or 90°).
6-inch vent/air piping — Reduce maximum allowable length by 15 feet for each additional elbow used.
8-inch vent/air piping — Reduce maximum allowable length by 7 feet for each additional elbow used.
NOTE
:
If the pipe manufacturer’s equivalent lengths for elbows is LONGER than the values listed above, use the
pipe manufacturer’s value for length reduction per elbow instead.
Boilers will
derate
as vent/air pipe length increases — see Figure 108, page 116 for derate amount vs piping length.
Note 2
Side air intake/through the roof vent
must use
Combustion Air Pressure Kit, see Figure 96, page 105 for Kit part number.
See Note 2.