L. Multiple Boiler and BMS Connections –
see ADVANCED Manual
4ERMINAL3TRIPS%0AND%0ON%XPANSION-ODULE
(Expansion module, right side)
1. The boiler control is capable of multiple boiler communication and control of up
to eight (8) boilers in one installation.
2. The boiler control is also capable of BMS communication.
3. See
SlimFit
Advanced Manual for multiple boiler installation and setup informa-
tion.
See SlimFit Advanced Manual for details
M. Additional heat demand contacts – OPTIONAL
4ERMINAL"LOCK00INS
(SlimFit control module, top left)
1. The control module can be set to activate another heat source using its additional
heat demand dry contacts through terminal block P16 pins 6 & 7.
2. Connect these terminals to call for heat from the other heat source.
3. Contact electrical ratings: 24VAC or less; 0.5 amp or less.
4. Set the control to activate the heat demand contacts as needed.
5. See SlimFit Advanced Manual to configure.
See Figure 52, page 48 for details
N. 0-10 VDC Output Section
4ERMINAL"LOCK00INS
(SlimFit control module, top left)
1. The control module can be set to activate another heat source using its 0-10VDC
Output through terminal block P16 pins 1 & 2.
2. Connect these terminals to 0-10VDC inputs on another heat source to control
its modulation rate.
3. Maximum electrical ratings: 10VDC; 108μ A.
4. Set the control to activate the output as needed.
5. See SlimFit Advanced Manual to configure.