6 Commissioning
| Commissioning with the TIA portal(PROFINET)
28
2547720000/03/09.2019
Manual Communication module UR20-4COM-IO-LINK
▶
Double-click the module, or drag it into the device over-
view.
The module is displayed in the device overview.
Adding IO-Link master with the TIA portal (example: PROFINET)
Parameterising IO-Link port with the TIA portal
The IO-Link ports are parameterised using the IO-Link master
parameters. An overview of all parameters is presented in
▶
Select the module in the device overview.
▶
In the inspection window, select the
General
tab.
▶
Select
Component parameters
.
The list of all parameters is displayed.
Editing module parameters
▶
Click the parameter that you would like to change and
select the desired setting.
▶
Use this method to edit all of the parameters that you
would like to change.
All settings only take effect once they have been
loaded into the component.
Integrating IO-Link device with the TIA portal
A IO-Link device is integrated using the suitable parameteri-
zation of the associated IO-Link port.
▶
Select the module in the device overview.
▶
In the inspection window, select the
General
tab.
▶
Select
Component parameters
.
The list of all parameters is displayed.
▶
Set the “Operating mode” parameter of the IO-Link port to
the value “IO-Link”.
▶
Set the “Process data length input” parameter to the
value “auto (default)”.
▶
Set the “Process data length output” parameter to the
value “auto (default)”.
▶
Change the other parameters as required.
All settings only take effect once they have been
loaded into the component.
Summary of Contents for UR20 Series
Page 1: ...Remote I O System u remote UR20 Communication module UR20 4COM IO LINK Manual Let s connect...
Page 8: ...8 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Page 10: ...10 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Page 20: ...20 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Page 48: ...48 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...
Page 54: ...54 2547720000 03 09 2019 Manual Communication module UR20 4COM IO LINK...