Connecting the SAI Distributor
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load
per pin 3 A
Reverse polarity protection
Yes
Current input
module approx. 50 mA
Digital inputs
6 channels
Plug-in stations
GT1, GT2, V/R1, V/R2, CN1, CN2
Grouping
one group for all six channels with a common earth
Permissible input voltage
-30 V DC to +30 V DC (protected against polarity reversal)
Input level Low
< 5 V DC acc. to EN 61131-2 Type 1
Input level High
> 15 V DC acc. to EN 61131-2 Type 1
Input current Low
< 15 mA acc. to EN 61131-2 Type 1
Input current High
2 mA to 15 mA acc. to EN 61131-2 Type 1
Max. input frequency
100 kHz
Separation of potentials to the module
electronics
None
Display elements
one yellow/green error/status LED per channel
Counter Channels
2 channels
Counter Width
32 bit
Switching frequency
Max. 100kHz, 2kHz when direction changes
Supported counter modes
Normal operation, quadrature counting mode
Current ranges
2 outputs (one per channel)
Plug-in stations
OUT1, OUT2
Grouping
one group for all 2 output channels with a common earth
Driver type
Highside
Current per channel
0.5 A
Residual current
module 4 A
Output voltage Low
0 V
Switching capacity, resistive load
max. 100 Hz
Switching capacity, inductive load
max. 1 Hz
Switching capacity, lamp load:
max. 8 Hz
5663600000/1.4/09.09
93
Summary of Contents for SAI Active Universal Pro Series
Page 2: ......
Page 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Page 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Page 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Page 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Page 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Page 177: ......