Connecting the SAI Distributor
5663600000/1.4/09.09
NOTE
The power supply is connected to the
sub-bus via a 4-pole M8 male connector
and a 4-pole M8 female connector. Use
the SUB-IN connection to feed in the
power supply and the SUB-OUT con-
nection to feed it forward. The power
supply and the digital inputs share a
common earth and are not electrically
isolated.
Connection of the supply voltage
The power supply is 24 V DC in accordance with EN
61131-2; the permissible range is 18 to 30 V DC.
The distributor is designed to offer protection against
polarity reversal.
Module connection from SUB-IN
Contact system
M8 male connector, 4-pole
Coding -
Pin assignment
Pin 1: + 24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected
with the FE
Module connection from SUB-OUT
Contact system
M8 female connector, 4-pole
Coding A
Pin assignment
Pin 1: + 24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected
with the FE
Table 34
Contact assignment for the Sub-bus
male connector
Table 35
Contact assignment for the Sub-bus
female connector
Module connection from AUX-IN
Contact system
M12 male connector, 5-pole
Coding A
Pin assignment
Pin 1: + 24 Vdc UQ1
Pin 2: + 24 Vdc UQ1
Pin 3: GND UQ1
Pin 4: GND UQ1
Pin 5: PE housing: Shield,
connected with the FE
Table 36
Contact assignment for the power sup-
ply male connector
57
Summary of Contents for SAI Active Universal Pro Series
Page 2: ......
Page 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Page 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Page 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Page 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Page 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Page 177: ......