Connecting the SAI Distributor
84
5663600000/1.4/09.09
Technical data
Supply voltage
24 V DC
Limit values
18 V DC to 30 V DC
Contact load
per pin 3 A
Reverse polarity protection
yes
Current input
module approx. 50 mA
Analogue inputs
4 channels
Plug-in stations
AI0, AI1, AI2 and AI3
Grouping
one group for four channels
Permissable common-mode voltage
+/- 50V
Permissible input voltage
-3 V DC to +3 V DC (protected against polarity reversal)
Sensor types
types J, K, L, B, E, N, R, S, T, U, +/-15mV…+/-250mV
Sampling period
54-620 ms adjustable per analogue input
Accuracy
< 0.5 % from the upper limit of effective range
Temperature coefficient
< 300 ppm/K of upper limit of effective range
Cold-junction compensation
external PT1000 connection on pin 1 and pin 3
Sensor current for PT1000
0.2mA
Resolution of thermocouple
0.1 °C
Resolution -mV-range
depending on range, 0.5 - 8uV
General technical data:
Ambient temperature during operation
0 to +60 °C acc. to EN 61131-2
Ambient temperature during storage
-25 to +85 °C acc. to EN 61131-2
Protection class
IP65 / IP67
Dimensions L x W x H
155 x 30 x 32 mm
Weight 150
g
Article order number
1938720000
Article designation
SAI-AU M12 SB 4THERMO
Table 65
Technical data, SAI-AU M12 SB 4THERMO
Summary of Contents for SAI Active Universal Pro Series
Page 2: ......
Page 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Page 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Page 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Page 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Page 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Page 177: ......