www.weg.net
38 | Energy Analyzer - MMW03-M22CH
5 FACTORY DEFAULT SETTINGS
Menu
Sub Menu 1
Sub
Menu 2
Description
Default
Value
Unit
Setting Range
BASIC
Ctr
Current transformer ratio
1
-
0.00 - 1.00
Utr
Voltage transformer ratio
1.0
-
0.00 - 1.00
Conn
Connection type options
3P4W
-
0.00 - 1.00
ALARMS
VLN ALM
HI
Voltage (phase-neutral) alarm
high limit
0.0
V
0 - 60
LO
Voltage (phase-neutral) alarm
low limit
0.0
V
45.0 - 65.0
hYSt
Voltage (phase-neutral) alarm
hysteresis value
5.0
V
45.0 - 65.0
dlY.t
Voltage (phase-neutral) alarm
delay time
5
sn
0.0 - 20.0
VLL ALM
HI
Voltage (phase-phase) alarm high
limit
0.0
V
0 - 60
LO
Voltage (phase-phase) alarm high
low limit
0.0
V
OFF/LOW/HIGH
hYSt
Voltage (phase-phase) alarm
hysteresis value
5.0
V
OFF/LOW/HIGH
dlY.t
Voltage (phase-phase) alarm
delay time
5
sn
1 - 60
I ALM
HI
Current alarm high limit
0.0
A
1200/2400/4800/9600/19200/38
LO
Current alarm low limit
0.0
A
400/57600
hYSt
Current alarm hysteresis value
0.1
A
1 - 247
dlY.t
Current alarm delay value
5
sn
NONE/EVEN/ODD
IN ALM
HI
Neutral current alarm high limit
0.0
A
OFF/TARIFF 2/COUNTER/RUN
HOUR
LO
Neutral current alarm low limit
0.0
A
10 - 2000
hYSt
Neutral current hysteresis value
0.1
A
RISING/FALLING/BOTH EDG
dlY.t
Neutral current alarm delay value
5
sn
OFF/TARIFF 2/COUNTER/RUN
HOUR
COSQ ALM
HI
cos φ alarm high limit
0.00
-
10 - 2000
LO
cos φ alarm low limit
0.00
-
RISING/FALLING/BOTH EDG
hYSt
cos φ alarm hysteresis value
0.01
-
0.00 - 1.00
dlY.t
cos φ alarm delay time
5
sn
0 - 60
ALARMS
PF ALM
HI
Power factor alarm high limit
0.00
-
0.00 - 1.00
LO
Power factor alarm low limit
0.00
-
0.00 - 1.00
hYSt
Power factor alarm hysteresis
value
0.01
-
0.00 - 1.00
dlY.t
Power factor alarm delay time
5
sn
0 - 60
FREQ ALM
HI
Frequency alarm high limit
50.0
Hz
45.0 - 65.0
LO
Frequency alarm low limit
50.0
Hz
45.0 - 65.0
hYSt
Frequency alarm hysteresis value
2.0
Hz
0.0 - 20.0
dlY.t
Frequency alarm delay time
5
sn
0 - 60
RELAYS
rLY1
Relay 1 setup
OFF
-
OFF/LOW/HIGH
rLY2
Relay 2 setup
OFF
-
OFF/LOW/HIGH
DEMAND
dEd.s
Demand time setup
15
dk
1 - 60
RS485
bAud
Baud rate options
38400
Baud
1200/2400/4800/9600/19200/38
400/57600
Id
Slave ID setup
1
-
1 - 247
PrtY
Parity check setup
NONE
-
NONE/EVEN/ODD
DI INPUT
INPUT1
tYPE
Digital input 1 options
OFF
-
OFF/TARIFF 2/COUNTER/RUN
HOUR
dLY
Digital input 1 detection delay
time
10
msn
10 - 2000
EdgE
Digital input 1 detection edge
RISING
-
RISING/FALLING/BOTH EDG
INPUT2
tYPE
Digital input 2 options
OFF
-
OFF/TARIFF 2/COUNTER/RUN
HOUR
dLY
Digital input 2 detection delay
time
10
msn
10 - 2000
Digital input 2 detection edge
RISING
-
RISING/FALLING/BOTH EDG
Summary of Contents for MMW03-M22CH
Page 2: ......
Page 3: ...User Manual Series MMW03 M22CH Language English Document 10006614878 00...
Page 4: ......
Page 41: ...www weg net NOTES Energy Analyzer MMW03 M22CH 41...
Page 42: ...www weg net NOTES 42 Energy Analyzer MMW03 M22CH...
Page 43: ...www weg net NOTES Energy Analyzer MMW03 M22CH 43...