WEG MMW03-M22CH User Manual Download Page 25

www.weg.net

Energy Analyzer - MMW03-M22CH | 25 

CAUTION!

Digital input is based on dry contact detection principle. Never apply signal to inputs. Otherwise there is risk of damaging 
the device.

Digital input type (tYPE):

 

„

Option to enable tariff 2 (TARIFF 2): If you choose this option for the digital input type, tariff2 energy counters 
will be enabled when the digital input is active (dry contact must be applied from related DIN+ and DIN-).

 

„

Option to enable the counter (COUNTER): If you choose this option for the digital input type, the counter will 
count the changes in the position of the digital input depending on the chosen detection edge.

 

„

 If you choose rising edge detection (RISING) for the detection edge, the counter will increase by 1 on each 
activation of the dry contact that is connected to the digital input.

 

„

 If you choose falling edge detection (FALLING) for the detection edge, the counter will increase by 1 on each 
de-activation of the dry contact that is connected to the digital input.

 

„

 If you choose both edges detection (BOTH EDGE) for the detection edge, the counter will increase by 1 on 
each activation and de-activaton of the dry contact that is connected to the digital input.

 

„

Run Hour enable option (RUN HOUR): If you choose this option for the digital input type, the “run hour 
counter” start counting when the digital input is active. (Dry contact must be applied from related DIN+ and 
DIN-).

Detection delay time (dLY):

The input is enabled or disabled based on the detection delay time which is set to account for contact spikes or 
noise in the digital input.

Detection edge (EdgE):

Use this menu item to choose the position where the digital input is detected active or passive. This menu is 
available only for the digital input mode “counter”. Other options always use the rising edge detection.

3.5.7 Pulse Output Settings Menu (PULSE)

Use this menu item to specify the on/off position, output parameter, pulse duration and step range settings for 
the pulse outputs. You can freely choose the settings for each pulse output independent of each other. Please 
see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.

The pulse output is activated with an increase in the predefined output parameter that is equal to each step range 
and deactivates after the predefined time.

Output parameter setup (OUT):

Use this menu item to set the parameter dependency of the output. The respective output is closed when you 
choose “OFF”.

Pulse duration setup (durA):

Use this menu item to specify the time the pulse is active.

Pulse step range (rAt):

Use this menu to specify the smallest possible increase for the input parameter that will
output a pulse.

3.5.8 Password Settings Menu (SECURITY)

Use this menu item to turn the password protection on/off, set a password activation time and change password 
settings editing options. Please see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.

4 digit password protects the product setup and counter menus against unauthorized access and modifications. 
When activated, a password query screen is displayed if someone attempts to change the values. After a successful 
login, the device will not ask for a password until the “password activation time” has elapsed. You can set this value in
the respective menu item. Please see Table 3-3 for the menu tree and SECTION 5 for the factory default settings.

Summary of Contents for MMW03-M22CH

Page 1: ...Motors Automation Energy Transmission Distribution Coatings User Manual Energy Analyzer MMW03 M22CH...

Page 2: ......

Page 3: ...User Manual Series MMW03 M22CH Language English Document 10006614878 00...

Page 4: ......

Page 5: ...ters 17 3 4 COUNTERS MENU COUNTERS 17 3 5 SETTINGS MENU SETTINGS 18 3 5 1 Basic Settings Menu BASIC 23 3 5 2 Alarm Settings Menu ALARMS 23 3 5 3 Alarm Relay Settings Menu RELAYS MMW03 M22CH 24 3 5 4 D...

Page 6: ...voltage frequency and power factor parameters 2 tariff meters These meters record Import Active Export Active Import Reactive Export Reactive Storing on hour counter on hour run hour counter total ene...

Page 7: ...e commissioning the device Do not open the device There are no serviceable parts by the user Keep the device away from humidity water vibrations and dust It is advisable to connect a circuit breaker o...

Page 8: ...w The menu pages change with up down right and left direction buttons 1 4 1 Key Functions The buttons placed front panel and their functions are explained at the table below At the Measurements Menus...

Page 9: ...Cos COS Max COS Min COS PF Power Factor PF PF Max PF Min PF Total PF Max Total PF Min Total PF Power P Active Power P P Max P Min P Demand P Total P Max Total P Min Total P Total Demand P Power Q Rea...

Page 10: ...TIVE 2 Tariff 2 Export Active Energy COUNTER 2 Counter 2 IMPORT REACT 1 Tariff 1 Import Reactive Energy IMPORT REACT 2 Tariff 2 Import Reactive Energy RUN HOUR Run Hour Counter EXPORT REACT 1 Tariff 1...

Page 11: ...ANT 4 P Q positive negative capacitive Cos capacitive PF positive QUADRANT 3 P Q negative negative inductive Cos inductive PF negative S P Q Figura 1 2 Four Quadrant Representation NOTE If the signs o...

Page 12: ...t it should be fixed to the panel wall with the screws DANGER Before wiring up voltage and current ends to MMW03 M22CH you must be sure that the power is cut DANGER The product is connected to current...

Page 13: ...hed the device Figure 1 1 2nd item if there is an error in the voltage phase during due to incorrect sequence Voltage phase sequence error icon will appear If this icon appears phase sequence voltage...

Page 14: ...ed It also states that inductive or capacitive phases are indicated next to the relevant indicators Table 1 3 for parameters displayed in the menus POWER Q Figura 3 1 Instantaneous Measurement Menus R...

Page 15: ...an be deleted by selecting CLEAR menu in the SETTINGS menu Reset and return to the factory settings can be made with RS 485 communication POWER Figura 3 2 Instantaneous Measurement Menus Active Power...

Page 16: ...PORT REACT 2 Tariff 2 Export Reactive Energy Tabela 3 1 Energy Meters Menu The following menu icons are active in ENERGY menu This icon appears with Tariff 1 counters This icon appears with Tariff 2 c...

Page 17: ...ght key for at least 2 sec to display the password authentication page Enter the password to proceed to the counter assignment 3 4 COUNTERS MENU COUNTERS There are counters under the COUNTERS menu bel...

Page 18: ...nt This icon appears with POWER INTERRUPTION COUNTER counter Figura 3 5 COUNTER2 Menu CAUTION Counters are displayed as 8 digits All counters are reset at 99 999 999 and then start over from zero Only...

Page 19: ...arm high limit LO Voltage phase phase alarm high low limit hYSt Voltage phase phase alarm hysteresis value dlY t Voltage phase phase alarm delay time I ALM Current alarm setup HI Current alarm high li...

Page 20: ...FF LOW Assign relay 2 to level low alarms HIGH Assign relay 2 to level high alarms DEMAND Demand setup dEd t Demand time setup RS485 RS485 setup bAud Baud rate options Id Slave ID setup PrYt Parity ch...

Page 21: ...Assign to tariff 2 import active energy counter EXP ACT2 Assign to tariff 2 export active energy counter IMP REA2 Assign to tariff 2 import reactive energy counter EXP REA2 Assign to tariff 2 export r...

Page 22: ...LAY Secreen setup MENU Menu setup ScrL Menu scroll setup OFF Menu scroll disable ON Menu scroll enable Scr P Menu display time Strt Home page setup VOLTAGELN Home page Voltage L N VOLTAGELL Home page...

Page 23: ...modbus addresses Voltage transformer ratio Utr The calculated voltages are multiplied by the voltage transformer ratio Utr to be indicated on the displays and the modbus addresses Connection Conn Thi...

Page 24: ...RS485 Settings Menu RS485 Use this menu item to set the baudrate slave ID and parity control settings in RS485 communication Please see Table 3 3 for the menu tree and SECTION 5 for the factory defaul...

Page 25: ...se this menu item to choose the position where the digital input is detected active or passive This menu is available only for the digital input mode counter Other options always use the rising edge d...

Page 26: ...perates or with a pressing any key Display backlight will be turned off if there is no pressing any key after set time It is preferred to have longer lasting power saving and LED lighting Continuous O...

Page 27: ...lete your choice Menus with numerical input values In these menus move through the digits to set the desired value Press the right key to choose and blink the first digit of the variable from the left...

Page 28: ...hanges Press the right key to blink the NO sign Then exit the menu using the left key without saving your changes NO CAUTION In the Delete Menu SETTINGS ALL or ALARMS option shuts down the device afte...

Page 29: ...se 1 THDV float RO 18 Phase 1 THDI float RO Phase 2 Basic Measurements 20 Phase 2 Voltage L N float RO 22 Phase 2 3 Voltage L L float RO 24 Phase 2 Current float RO 26 Phase 2 Cos float RO 28 Phase 2...

Page 30: ...cs 19 float RO 130 Phase 1 Current Harmonics 21 float RO 132 Phase 1 Current Harmonics 23 float RO 134 Phase 1 Current Harmonics 25 float RO 136 Phase 1 Current Harmonics 27 float RO 138 Phase 1 Curre...

Page 31: ...Harmonics 3 float RO 242 Phase 3 Current Harmonics 5 float RO 244 Phase 3 Current Harmonics 7 float RO 246 Phase 3 Current Harmonics 9 float RO 248 Phase 3 Current Harmonics 11 float RO 250 Phase 3 Cu...

Page 32: ...O 358 Phase 1 Min Active Power float RO 360 Phase 1 Min Reactive Power float RO 362 Phase 1 Min Apparent Power float RO 364 Phase 1 Min THDV float RO 366 Phase 1 Min THDI float RO Phase 2 Maximum Meas...

Page 33: ...ord in the Settings Protection field and then enter 2222 in the Enable Counter Change field You can then enter the value 480 Export Active Energy T2 Tariff 2 32 bit integer R W 482 Import Reactive Ene...

Page 34: ...rd Value 32 bit integer R W 552 Baud Rate 32 bit integer R W 554 Slave ID 32 bit integer R W 556 Parity Control 32 bit integer R W 558 Digital Input 1 Type 32 bit integer R W 560 Digital Input 1 Delay...

Page 35: ...nteger WO 1004 Reset Max Values 32 bit integer WO 1006 Reset Min Values 32 bit integer WO 1008 Reset Demand Values 32 bit integer WO 1010 Reset Settings 32 bit integer WO 1012 Reset Alarm Limits MMW03...

Page 36: ...status 25 21 Reserve 20 SEQ Phase Order Alarm 19 I3 OFF 3 No current in Line 3 18 I2 OFF 2 No current in Line 2 17 I1 OFF 1 No current in Line 1 16 V3 OFF 3 No voltage in Line 3 15 V2 OFF 2 No voltag...

Page 37: ...N HOUR 562 Say sal Giri 1 Edge 0 RISING 1 FALLING 2 BOTH EDG 564 Say sal Giri 1 Edge 0 OFF 1 TARIFF 2 2 COUNTER 3 RUN HOUR 568 Digital Input 2 Edge 0 RISING 1 FALLING 2 BOTH EDG Adress Register name W...

Page 38: ...RISING FALLING BOTH EDG dlY t Neutral current alarm delay value 5 sn OFF TARIFF 2 COUNTER RUN HOUR COSQ ALM HI cos alarm high limit 0 00 10 2000 LO cos alarm low limit 0 00 RISING FALLING BOTH EDG hY...

Page 39: ...EXP REA2 DIN1 DIN2 durA Pulse duration of the pulse output 2 50 msn 50 2500 Step range for pulse output 2 1 kWh kVArh Qty 1 99 999 999 SIFRE Act Enable disable password protection NO NO YES Pin t Time...

Page 40: ...orage Temperature 30 C 80 C Protection Class IP40 Relative Humidity 95 non condensing Measurement Accuracy Symbol Measurement Type Class According to IEC 61557 12 Measurement Range Other Standards P T...

Page 41: ...www weg net NOTES Energy Analyzer MMW03 M22CH 41...

Page 42: ...www weg net NOTES 42 Energy Analyzer MMW03 M22CH...

Page 43: ...www weg net NOTES Energy Analyzer MMW03 M22CH 43...

Page 44: ...ze Hesse Phone 49 5681 99520 info akh antriebstechnik de GHANA Accra Phone 233 30 2766490 info zestghana com gh INDIA Bangalore Karnataka Phone 91 80 41282007 info in weg net Hosur Tamil Nadu Phone 91...

Reviews: