36 | Energy Analyzer - MMW03-M22CH
4.1.1 Status/Alarm Flags
“Alarm Flags” modbus address showing the alarm conditions and alarm conditions represented with bits are
given below.
458 Alarm Flags
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Dl2
Status
Dl1
Status
Relay 2
Status
Relay 2
Status
DO2
Status
DO1
Status
Reserve/OFF
SEQ
I3
OFF
I2
OFF
I1
OFF
V3
OFF
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
V2
OFF
V1
OFF
Freq
Low
Freq
High
PF
Low
PF
High
Cos
φ
Low
Cos
φ
High
I(Nötr)
Low
I(Nötr)
High
I
Low
I
High
V(L-L)
Low
V(L-L)
High
V(L-N)
Low
V(L-N)
High
Tabela 4.2: Alarm Flags
bit
Description
31
: DI2 Status: Digitial input 2 signal condition (active or passive).
30
: DI1 Status: Digitial input 1 signal condition (active or passive).
29
: DI1 Status: Digitial input 1 signal condition (active or passive).
28
: Relay 1 Status: Relay 1 active/pasive status.
27
: DO2 Status: Digital Output 2 active/pasive status.
26
: DO1 Status: Digital Output 1 active/pasive status.
25-21 : Reserve.
20
: SEQ - Phase Order Alarm.
19
: I3 OFF - 3. No current in Line-3.
18
: I2 OFF - 2. No current in Line-2.
17
: I1 OFF - 1. No current in Line-1.
16
: V3 OFF - 3. No voltage in Line-3.
15
: V2 OFF - 2. No voltage Line-2.
14
: V1 OFF - 1. No voltage in Line-1.
13
: Freq Low - Low frequency alarm.
12
: Freq High - High frequency alarm.
11
: PF Low - Low power factor alarm.
10
: PF High - High power factor alarm.
9
: Cos
φ
Low - Low Cos
φ
alarm.
8
: Cos
φ
High - High Cos
φ
alarm.
7
: I(N) Low - Low neutral current alarm.
6
: I(N) High - High neutral current alarm.
5
: I Low - Low current alarm.
4
: I High - High current alarm.
3
: V(L-L) Low - Low phase-phase voltage alarm.
2
: V(L-L) High - High phase-phase voltage alarm.
1
: V(L-N) Low - Low phase-neutral voltage alarm.
0
: V(L-N) High - High phase-neutral voltage alarm.
CAUTION!
If the device was not restarted after entering the password or the “password activation time” has not elapsed, this will read
“0” to indicate that password protection is disabled in the “Settings protection” address (modbus adr: 604). In this case,
you don’t need to re-enter the password.
Password activation time resets and restarts each time a modbus write action is performed or a key is pressed.
Summary of Contents for MMW03-M22CH
Page 2: ......
Page 3: ...User Manual Series MMW03 M22CH Language English Document 10006614878 00...
Page 4: ......
Page 41: ...www weg net NOTES Energy Analyzer MMW03 M22CH 41...
Page 42: ...www weg net NOTES 42 Energy Analyzer MMW03 M22CH...
Page 43: ...www weg net NOTES Energy Analyzer MMW03 M22CH 43...