![WEG MMW03-M22CH User Manual Download Page 33](http://html1.mh-extra.com/html/weg/mmw03-m22ch/mmw03-m22ch_user-manual_950745033.webp)
www.weg.net
Energy Analyzer - MMW03-M22CH | 33
Adress
Parametre
Type
Read / Write
Write Condition
422
Min. System Frequency
float
RO
424
Min. Neutral Current
float
RO
Alarm Flags (MMW03-M22CH)
426
Alarm Flags
32 bit integer
RO
See Table 4.2
Demand Measurements
428
Phase 1 Current Demand
float
RO
430
Phase 2 Current Demand
float
RO
432
Phase 3 Current Demand
float
RO
434
Total Current Demand
float
RO
436
Phase 1 Active Power Demand
float
RO
438
Phase 2 Active Power Demand
float
RO
440
Phase 3 Active Power Demand
float
RO
442
Total Active Power Demand
float
RO
444
Phase 1 Reactive Power Demand
float
RO
446
Phase 2 Reactive Power Demand
float
RO
448
Phase 3 Reactive Power Demand
float
RO
450
Total Reactive Power Demand
float
RO
452
Phase 1 Apparent Power Demand
float
RO
454
Phase 2 Apparent Power Demand
float
RO
456
Phase 3 Apparent Power Demand
float
RO
458
Total Apparent Power Demand
float
RO
Digital Input
460
Digital Input 1 Counter
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
462
Digital Input 2 Counter
32 bit integer
R / W
464
Run Hour Counter
32 bit integer
R / W
466
On Hour Counter
32 bit integer
RO
468
Power Interruptions Counter
32 bit integer
RO
Energy Meters
Tariff 1 Total Energy Values (Phase3)
470
Import Active Energy T1 (Tariff 1)
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
472
Export Active Energy T1 (Tariff 1)
32 bit integer
R / W
474
Import Reactive Energy T1 (Tariff 1)
32 bit integer
R / W
476
Export Reactive Energy T1 (Tariff 1)
32 bit integer
R / W
Tariff 2 Total Energy Values (Phase3)
478
Import Active Energy T2 (Tariff 2)
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
480
Export Active Energy T2 (Tariff 2)
32 bit integer
R / W
482
Import Reactive Energy T2 (Tariff 2)
32 bit integer
R / W
484
Export Reactive Energy T2 (Tariff 2)
32 bit integer
R / W
Tariff 1 Phase1 Energy Values
486
Import Active Energy T1-Phase1 (Tariff 1)
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
488
Export Active Energy T1-Phase1 (Tariff 1)
32 bit integer
R / W
490
Import Reactive Energy T1-Phase1 (Tariff 1)
32 bit integer
R / W
492
Export Reactive Energy T1-Phase1 (Tariff 1)
32 bit integer
R / W
Tariff 1 Phase 2 Energy Values
494
Import Active Energy T1-Phase2 (Tariff 1)
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
496
Export Active Energy T1-Phase2 (Tariff 1)
32 bit integer
R / W
498
Import Reactive Energy T1-Phase2 (Tariff 1)
32 bit integer
R / W
500
Export Reactive Energy T1-Phase2 (Tariff 1)
32 bit integer
R / W
Tariff 1 Phase 3 Energy Values
502
Import Active Energy T1-Phase3 (Tariff 1)
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
504
Export Active Energy T1-Phase3 (Tariff 1)
32 bit integer
R / W
506
Import Reactive Energy T1-Phase3 (Tariff 1)
32 bit integer
R / W
508
Export Reactive Energy T1-Phase3 (Tariff 1)
32 bit integer
R / W
Tariff 2 Phase 1 Energy Values
510
Import Active Energy T2-Phase1 (Tariff 2)
32 bit integer
R / W
If password protection is active, enter the
password in the “Settings Protection” field
and then enter “2222” in the “Enable Counter
Change” field. You can then enter the value.
512
Export Active Energy T2-Phase1 (Tariff 2)
32 bit integer
R / W
514
Import Reactive Energy T2-Phase1 (Tariff 2)
32 bit integer
R / W
516
Export Reactive Energy T2-Phase1 (Tariff 2)
32 bit integer
R / W
Summary of Contents for MMW03-M22CH
Page 2: ......
Page 3: ...User Manual Series MMW03 M22CH Language English Document 10006614878 00...
Page 4: ......
Page 41: ...www weg net NOTES Energy Analyzer MMW03 M22CH 41...
Page 42: ...www weg net NOTES 42 Energy Analyzer MMW03 M22CH...
Page 43: ...www weg net NOTES Energy Analyzer MMW03 M22CH 43...