Webstone® E-X-P

 Series service valve kits are designed to simplify the installation and 

maintenance of tankless water heaters (TWH) or the domestic hot water output of combi 

boilers. A variety of models, kits, pressure relief valves (PRV), and accessories are 

available to provide solutions for most installation needs.

IMPORTANT:

 Follow all federal/national, state, and local codes when installing, 

testing, or performing work on systems. All parts are covered by a warranty against 

manufacturing defects, provided they are installed by a licensed plumber and operated 

under normal working conditions. If you have any questions or comments, please 

contact us at (800) 225-9529 or visit us on the web at www.webstonevalves.com.

WARNING:

 

Drain valves (if applicable) should remain closed during normal operation.  

Do not rely on the drain cap to stop the water from draining. When draining, always 

remove drain caps slowly to insure that no pressure exists.

Boiler Hydronic Connections: 

E-X-P Series service valves may be used for boiler 

connections, only when paired with a boiler-specific pressure relief valve with suitable 

pressure and BTU specifications (i.e. Webstone Item # H-20733, included in PR3 kits). See 

boiler manual for system requirements.

It is recommended that these instructions be stored along with other documents related 

to your heating appliance’s installation and maintenance.

INSTALLATION

 - refer to drawings at right for model details

1.

  Apply PTFE tape or sealant to any threaded pipe connections.

2.

  For installations utilizing PRV relocation adapter 

D

, thread 

D

 on heating  

appliance hot outlet. Ensure PRV Port Plug 

E

 is installed in Hot Valve 

B

 PRV port. 

Note:

 

PRV relocation adapter

 

D

 

takes the place of hot union fitting when installed 

with E-X-P E2™ service valves.

3. 

For installations with Pressure Relief Valve: 
Thread Pressure Relief Valve 

C

 into the Hot Valve 

B

 PRV port or PRV relocation 

adapter 

D

 as applicable. For item H-20723-CN Commercial PRV (sold separately) 

thread PRV body onto the close nipple until tight. Then thread the other end of the 
close nipple onto 

B

 or 

D

.

4

  Loosen Union Nut on Hot Valve 

B

 and connect union fitting to heating appliance 

hot outlet. If nut is removed, carefully reassemble as shown. Ensure washer or 
o-ring is positioned correctly and undamaged.

5.

  Position Hot Valve 

B

 as desired. Tighten union nut using approximately  

15 ft/lbs of torque.

6. 

Repeat steps 4 and 5 for the Cold Valve 

A

, connecting to  

heating appliance cold inlet.

7. 

Connect Cold Valve 

A

 to cold water supply.

8. 

Connect Hot Valve 

B

 to hot water piping.

9. 

Ensure that both drain valve lever handles are in the closed position  
(perpendicular to the drain portion of the body).

PRV INSTALLATION REQUIREMENTS & MAINTENANCE

WARNING:

 

A suitable pressure relief valve (PRV) is required for all installations, see 

heating appliance installation manual for specific system requirements. 

The PRV must be installed in Hot Valve 

B

 PRV port, PRV relocation adapter 

D

, or PRV 

port integrated directly into the heating appliance. Installation must maintain a 3/4" 

port size with no shut-off valve or line restriction in-between the appliance and the PRV. 

The discharge line from the PRV should pitch downward and terminate 6" above drains, 

or per local code height, where discharge will be clearly visible. The discharge end of 

the line shall be plain (unthreaded) and a minimum of 3/4" in diameter. The discharge 

line material must be suitable for water at least 180

°

F. The discharge line shall be as 

short and straight as possible such that the arrangement does not reduce the relieving 

capacity of the pressure relief valve. No valve of any type may be installed in the 

discharge line of the pressure relief valve.
It is recommended that the PRV is manually operated once a year. In doing so, it will be 

necessary to take precautions with regard to the discharge of potentially scalding hot 

water under pressure. Ensure discharge has a place to flow. Contact with your body or 

other property may cause damage or harm. 

WARNING:

 Cancer and Reproductive

Harm - www.P65Warnings.ca.gov  

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO
LD

HO

T

CO
LD

HO

T

TO

 DR
AIN

CO

LD

HO
T

TO

 DR
AIN

PRV RELOCATION 

ADAPTER

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

D

COLD VALVE

Blue Drain Handle

A

COMMERICAL

PRESSURE 

RELIEF VALVE

F

HOT VALVE

Red Drain Handle

B

PORT 

PLUG

E

CLOSE 

NIPPLE

G

O-RING

UNION FITTING

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

UNION FITTING

UNION FITTING

WASHER

UNION NUT

UNION NUT

WASHER

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

COLD VALVE

A

HOT VALVE

B

UNION

FITTING

UNION NUT

O-RING

UNION

FITTING

UNION NUT

COLD VALVE

Blue Wing Handle

A

HOT VALVE

Red Wing Handle

B

COLD UNION 

FITTING

w/ Blue Insulator

HOT UNION FITTING

w/ Red Insulator

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

A

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

HOT VALVE

B

PRV PORT

PRV PORT

PRV PORT*

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO
LD

HO

T

CO
LD

HO

T

TO

 DR
AIN

CO

LD

HO
T

TO

 DR
AIN

PRV RELOCATION 

ADAPTER

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

D

COLD VALVE

Blue Drain Handle

A

COMMERICAL

PRESSURE 

RELIEF VALVE

F

HOT VALVE

Red Drain Handle

B

PORT 

PLUG

E

CLOSE 

NIPPLE

G

O-RING

UNION FITTING

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

UNION FITTING

UNION FITTING

WASHER

UNION NUT

UNION NUT

WASHER

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

COLD VALVE

A

HOT VALVE

B

UNION

FITTING

UNION NUT

O-RING

UNION

FITTING

UNION NUT

COLD VALVE

Blue Wing Handle

A

HOT VALVE

Red Wing Handle

B

COLD UNION 

FITTING

w/ Blue Insulator

HOT UNION FITTING

w/ Red Insulator

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

A

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

HOT VALVE

B

PRV PORT

PRV PORT

PRV PORT*

INSTALLATION 

INSTRUCTIONS

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO
LD

HO

T

CO
LD

HO

T

TO

 DR
AIN

CO

LD

HO
T

TO

 DR
AIN

PRV RELOCATION 

ADAPTER

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

D

COLD VALVE

Blue Drain Handle

A

COMMERICAL

PRESSURE 

RELIEF VALVE

F

HOT VALVE

Red Drain Handle

B

PORT 

PLUG

E

CLOSE 

NIPPLE

G

O-RING

UNION FITTING

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

UNION FITTING

UNION FITTING

WASHER

UNION NUT

UNION NUT

WASHER

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

COLD VALVE

A

HOT VALVE

B

UNION

FITTING

UNION NUT

O-RING

UNION

FITTING

UNION NUT

COLD VALVE

Blue Wing Handle

A

HOT VALVE

Red Wing Handle

B

COLD UNION 

FITTING

w/ Blue Insulator

HOT UNION FITTING

w/ Red Insulator

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

A

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

HOT VALVE

B

PRV PORT

PRV PORT

PRV PORT*

For appliances with 

top or bottom mounted 

water connections 

and integrated PRV 

and drain ports

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

TO

 DR
AIN

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO

LD

HO
T

CO
LD

HO

T

CO
LD

HO

T

TO

 DR
AIN

CO

LD

HO
T

TO

 DR
AIN

PRV RELOCATION 

ADAPTER

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

COLD INLET

HOT OUTLET

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

D

COLD VALVE

Blue Drain Handle

A

COMMERICAL

PRESSURE 

RELIEF VALVE

F

HOT VALVE

Red Drain Handle

B

PORT 

PLUG

E

CLOSE 

NIPPLE

G

O-RING

UNION FITTING

UNION FITTING

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

UNION FITTING

UNION FITTING

WASHER

UNION NUT

UNION NUT

WASHER

COLD VALVE

Blue Drain Handle

A

HOT VALVE

Red Drain Handle

B

COLD VALVE

A

HOT VALVE

B

UNION

FITTING

UNION NUT

O-RING

UNION

FITTING

UNION NUT

COLD VALVE

Blue Wing Handle

A

HOT VALVE

Red Wing Handle

B

COLD UNION 

FITTING

w/ Blue Insulator

HOT UNION FITTING

w/ Red Insulator

WASHER

UNION NUT

WASHER

UNION NUT

COLD VALVE

A

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

PRESSURE 

RELIEF VALVE

C

HOT VALVE

B

PRV PORT

PRV PORT

PRV PORT*

* Available without PRV port for appliances with integrated PRV Ports

Refer to E-X-P E3

 

drawing below 

if installing with 

H-28023W PRV 

Relocation Adapter

W W W . W E B S T O N E V A L V E S . C O M

Summary of Contents for E-X-P Series

Page 1: ...nstallation manual for specific system requirements The PRV must be installed in Hot Valve B PRV port PRV relocation adapter D or PRV port integrated directly into the heating appliance Installation must maintain a 3 4 port size with no shut off valve or line restriction in between the appliance and the PRV The discharge line from the PRV should pitch downward and terminate 6 above drains or per l...

Page 2: ... valve 11 Remove the hose from the Cold A drain Replace cap washer securely onto the drain valve outlet 12 Remove the pump and hose from the pail Dispose of the cleansing solution safely and properly Flushing This procedure will flush the appliance with fresh cold water 13 Put the Hot B drain hose end back into the empty pail or place in drain Open the Cold A main water valve Flush with at least 2...

Page 3: ...tallée dans le port de la soupape de décompression PRV de la vanne d eau chaude B l adaptateur de transfert de la soupape de décompression PRV D ou directement dans le port de la soupape de décompression PRV intégré de l appareil de chauffage L installation doit soutenir un port de 3 4 po sans un robinet d arrêt ou un circuit de limitation entre l appareil et la soupape de décompression PRV La con...

Page 4: ...net de vidange de A l eau froide 11 Retirez le boyau du drain de l eau A froide Replacez fermement le bouchon et la rondelle sur la sortie du robinet de vidange 12 Retirez la pompe et le boyau du seau Éliminez la solution de nettoyage de manière sûre et appropriée Rinçage Cette procédure rince l appareil avec de l eau froide fraiche 13 Placez à nouveau l extrémité du boyau de drain de l eau B chau...

Page 5: ...nsulte el manual de instalación del equipo de calefacción para conocer los requerimientos específicos La PRV debe instalarse en el puerto de PRV de válvula caliente B en el adaptador de reubicación de PRV D o en el puerto de PRV integrado directamente en el equipo de calefacción La instalación debe mantener un tamaño de puerto de 3 4 sin válvula de apagado ni restricción de línea entre el equipo y...

Page 6: ...ía A Vuelva a colocar la tapa y la rondana de forma seguro en la salida de la válvula de drenado 12 Remueva la bomba y la manguera de la cubeta Deseche la solución de limpieza de forma segura y adecuada Enjuagado Este procedimiento enjuagará el equipo con agua fría limpia 13 Ponga el extremo de la manguera de la válvula de drenado caliente B de nuevo en la cubeta vacía o colóquela en el drenaje Ab...

Reviews: