Webstone® E-X-P
™
Series service valve kits are designed to simplify the installation and
maintenance of tankless water heaters (TWH) or the domestic hot water output of combi
boilers. A variety of models, kits, pressure relief valves (PRV), and accessories are
available to provide solutions for most installation needs.
IMPORTANT:
Follow all federal/national, state, and local codes when installing,
testing, or performing work on systems. All parts are covered by a warranty against
manufacturing defects, provided they are installed by a licensed plumber and operated
under normal working conditions. If you have any questions or comments, please
contact us at (800) 225-9529 or visit us on the web at www.webstonevalves.com.
WARNING:
Drain valves (if applicable) should remain closed during normal operation.
Do not rely on the drain cap to stop the water from draining. When draining, always
remove drain caps slowly to insure that no pressure exists.
Boiler Hydronic Connections:
E-X-P Series service valves may be used for boiler
connections, only when paired with a boiler-specific pressure relief valve with suitable
pressure and BTU specifications (i.e. Webstone Item # H-20733, included in PR3 kits). See
boiler manual for system requirements.
It is recommended that these instructions be stored along with other documents related
to your heating appliance’s installation and maintenance.
INSTALLATION
- refer to drawings at right for model details
1.
Apply PTFE tape or sealant to any threaded pipe connections.
2.
For installations utilizing PRV relocation adapter
D
, thread
D
on heating
appliance hot outlet. Ensure PRV Port Plug
E
is installed in Hot Valve
B
PRV port.
Note:
PRV relocation adapter
D
takes the place of hot union fitting when installed
with E-X-P E2™ service valves.
3.
For installations with Pressure Relief Valve:
Thread Pressure Relief Valve
C
into the Hot Valve
B
PRV port or PRV relocation
adapter
D
as applicable. For item H-20723-CN Commercial PRV (sold separately)
thread PRV body onto the close nipple until tight. Then thread the other end of the
close nipple onto
B
or
D
.
4
Loosen Union Nut on Hot Valve
B
and connect union fitting to heating appliance
hot outlet. If nut is removed, carefully reassemble as shown. Ensure washer or
o-ring is positioned correctly and undamaged.
5.
Position Hot Valve
B
as desired. Tighten union nut using approximately
15 ft/lbs of torque.
6.
Repeat steps 4 and 5 for the Cold Valve
A
, connecting to
heating appliance cold inlet.
7.
Connect Cold Valve
A
to cold water supply.
8.
Connect Hot Valve
B
to hot water piping.
9.
Ensure that both drain valve lever handles are in the closed position
(perpendicular to the drain portion of the body).
PRV INSTALLATION REQUIREMENTS & MAINTENANCE
WARNING:
A suitable pressure relief valve (PRV) is required for all installations, see
heating appliance installation manual for specific system requirements.
The PRV must be installed in Hot Valve
B
PRV port, PRV relocation adapter
D
, or PRV
port integrated directly into the heating appliance. Installation must maintain a 3/4"
port size with no shut-off valve or line restriction in-between the appliance and the PRV.
The discharge line from the PRV should pitch downward and terminate 6" above drains,
or per local code height, where discharge will be clearly visible. The discharge end of
the line shall be plain (unthreaded) and a minimum of 3/4" in diameter. The discharge
line material must be suitable for water at least 180
°
F. The discharge line shall be as
short and straight as possible such that the arrangement does not reduce the relieving
capacity of the pressure relief valve. No valve of any type may be installed in the
discharge line of the pressure relief valve.
It is recommended that the PRV is manually operated once a year. In doing so, it will be
necessary to take precautions with regard to the discharge of potentially scalding hot
water under pressure. Ensure discharge has a place to flow. Contact with your body or
other property may cause damage or harm.
WARNING:
Cancer and Reproductive
Harm - www.P65Warnings.ca.gov
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
TO
DR
AIN
PRV RELOCATION
ADAPTER
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
D
COLD VALVE
Blue Drain Handle
A
COMMERICAL
PRESSURE
RELIEF VALVE
F
HOT VALVE
Red Drain Handle
B
PORT
PLUG
E
CLOSE
NIPPLE
G
O-RING
UNION FITTING
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
UNION FITTING
UNION FITTING
WASHER
UNION NUT
UNION NUT
WASHER
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
COLD VALVE
A
HOT VALVE
B
UNION
FITTING
UNION NUT
O-RING
UNION
FITTING
UNION NUT
COLD VALVE
Blue Wing Handle
A
HOT VALVE
Red Wing Handle
B
COLD UNION
FITTING
w/ Blue Insulator
HOT UNION FITTING
w/ Red Insulator
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
A
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
HOT VALVE
B
PRV PORT
PRV PORT
PRV PORT*
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
TO
DR
AIN
PRV RELOCATION
ADAPTER
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
D
COLD VALVE
Blue Drain Handle
A
COMMERICAL
PRESSURE
RELIEF VALVE
F
HOT VALVE
Red Drain Handle
B
PORT
PLUG
E
CLOSE
NIPPLE
G
O-RING
UNION FITTING
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
UNION FITTING
UNION FITTING
WASHER
UNION NUT
UNION NUT
WASHER
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
COLD VALVE
A
HOT VALVE
B
UNION
FITTING
UNION NUT
O-RING
UNION
FITTING
UNION NUT
COLD VALVE
Blue Wing Handle
A
HOT VALVE
Red Wing Handle
B
COLD UNION
FITTING
w/ Blue Insulator
HOT UNION FITTING
w/ Red Insulator
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
A
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
HOT VALVE
B
PRV PORT
PRV PORT
PRV PORT*
INSTALLATION
INSTRUCTIONS
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
TO
DR
AIN
PRV RELOCATION
ADAPTER
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
D
COLD VALVE
Blue Drain Handle
A
COMMERICAL
PRESSURE
RELIEF VALVE
F
HOT VALVE
Red Drain Handle
B
PORT
PLUG
E
CLOSE
NIPPLE
G
O-RING
UNION FITTING
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
UNION FITTING
UNION FITTING
WASHER
UNION NUT
UNION NUT
WASHER
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
COLD VALVE
A
HOT VALVE
B
UNION
FITTING
UNION NUT
O-RING
UNION
FITTING
UNION NUT
COLD VALVE
Blue Wing Handle
A
HOT VALVE
Red Wing Handle
B
COLD UNION
FITTING
w/ Blue Insulator
HOT UNION FITTING
w/ Red Insulator
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
A
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
HOT VALVE
B
PRV PORT
PRV PORT
PRV PORT*
For appliances with
top or bottom mounted
water connections
and integrated PRV
and drain ports
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
CO
LD
HO
T
TO
DR
AIN
CO
LD
HO
T
TO
DR
AIN
PRV RELOCATION
ADAPTER
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
COLD INLET
HOT OUTLET
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
D
COLD VALVE
Blue Drain Handle
A
COMMERICAL
PRESSURE
RELIEF VALVE
F
HOT VALVE
Red Drain Handle
B
PORT
PLUG
E
CLOSE
NIPPLE
G
O-RING
UNION FITTING
UNION FITTING
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
UNION FITTING
UNION FITTING
WASHER
UNION NUT
UNION NUT
WASHER
COLD VALVE
Blue Drain Handle
A
HOT VALVE
Red Drain Handle
B
COLD VALVE
A
HOT VALVE
B
UNION
FITTING
UNION NUT
O-RING
UNION
FITTING
UNION NUT
COLD VALVE
Blue Wing Handle
A
HOT VALVE
Red Wing Handle
B
COLD UNION
FITTING
w/ Blue Insulator
HOT UNION FITTING
w/ Red Insulator
WASHER
UNION NUT
WASHER
UNION NUT
COLD VALVE
A
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
PRESSURE
RELIEF VALVE
C
HOT VALVE
B
PRV PORT
PRV PORT
PRV PORT*
* Available without PRV port for appliances with integrated PRV Ports
Refer to E-X-P E3
™
drawing below
if installing with
H-28023W PRV
Relocation Adapter