Webasto Frigo Top 10 Workshop Manual Download Page 16

Frigo Top 10 - 43 | Pordoi 2000 - 4000 16 

10.4  Standard parameter settings

The standard parameter settings differ depending on the refrigerant. The tables below show the standard settings for refrigerant:

 

R134a

 

R134a and system with defrost

 

R404A

Making changes to these settings affects the functional safety of the system. Only make changes to the settings if you are familiar with 
the outcome!

10.4.1 Regulation

Label Description

Refrigerant

Program level

R134a

R134a with defrost

R404A

1

2

HY

Differential

2

2

2

2

LS

Minimum set point

0

0

-20

1

US

Maximum set point

30

30

30

1

ot

Thermostat probe calibration

0

0

0

2

P2P

Evaporator probe presence

y

y

y

1

oE

Evaporator probe calibration

0

0

0

2

OdS

Outputs delay at start up

0

0

0

2

db

Dead band (neutral zone)

n

n

y in case of 

heating kit

 

2

AC

Anti-short cycle delay

1

1

1

2

CCt

Continuous cycle duration

0

0

0

2

CCS

Set point for continuous cycle

0

0

0

2

COn

Compressor ON time with faulty probe

15

15

15

2

CoF

Compressor OFF time with faulty probe

30

30

30

2

10.4.2 Display

Label Description

Refrigerant

Program level

R134

R134a with defrost

R404A

1

2

CF

Temperature measurement unit

°C

°C

°C

2

rES

Resolution

dE

dE

dE

2

Lod

Probe displayed

P1

P1

P1

2

10.4.3 Defrost

Label Description

Refrigerant

Program level

R134

R134a with defrost

R404A

1

2

tdF

Defrost type

EL

in

in

2

dtE

Defrost termination temperature

2

5

5

1

idF

Interval between defrost cycles

1

3

3

1

MdF

(Maximum) length for defrost

8

5

5

1

dSd

Start defrost delay

0

0

0

2

dFd

Displaying during defrost

dEF

dEF

dEF

2

dAd

MAX display delay after defrost

1

1

1

2

Fdt

Draining time

1

1

1

1

dPo

First defrost after start-up

n

n

n

2

dAF

Defrost delay after fast freezing

0

0

0

2

Summary of Contents for Frigo Top 10

Page 1: ...Workshop Manual Transport Refrigeration Frigo Top 10 43 Pordoi 2000 4000 English F...

Page 2: ...vel menus 6 4 1 Entering the 1st service level 6 4 2 Entering the 2nd service level 6 4 3 Change a parameter setting 6 4 4 Exit a service menu 6 5 Set and reset the service interval 7 5 1 Enter the se...

Page 3: ...l Result damage to the refrigeration system X X Follow the operating instructions and instructions described in this document 2 Safety 2 1 General safety The repair and commissioning personnel must ha...

Page 4: ...compartment 3 3 Service levels The control element has an extensive set of parameters to regu late and control the refrigeration process The parameters are split in 2 levels Level 1 Level 2 Access th...

Page 5: ...pressor operation count appears on the display preceded by a minus sign Example If the saved value is 1511 hours of operation the first time the button is pressed 001 thousands is displayed The second...

Page 6: ...irst parameter of the 1st service level The degree symbol starts blinking 4 2 Entering the 2nd service level Fig 06 2nd level service menu Fig 07 First parameter of the 2nd level service menu X XPress...

Page 7: ...ween SEr change interval rSt reset interval 5 3 Reset the service interval Fig 14 Reset interval No Fig 15 Reset interval Yes 3 3 Make sure that the screen shows rSt ATTENTION Do not reset the service...

Page 8: ...eters from the hot key into the control element Upload parameters from the control element into the hot key Uploading parameters from the control element into the hot key provides a back up for eventu...

Page 9: ...t restarts and uses the new parameters X XRemove the hot key 6 3 Upload parameters to the hot key 3 3 Program the control element as desired with the keys on the front 3 3 Leave the control element on...

Page 10: ...ng the sensor X XContact a Webasto service partner HA Maximum temperature alarm Temperature in cooling compartment is too high LA Minimum temperature alarm Temperature in cooling compartment is too lo...

Page 11: ...input Potential free contact NTC probe 40 110 C 40 230 F Relay outputs PTC probe 50 150 C 58 302 F Compressor 8 3 A 16 6 A or 20 8 A 250 VAC Defrost 8 3 A 250 VAC Fan 8 3 250 VAC Fig 23 F 32 74 71 29...

Page 12: ...emeratures compared to the set temperature To be used in case of heating kit n neutral zone disabled cooling only y neutral zone enabled heating kit installed 2 AC Anti short cycle delay minimum inter...

Page 13: ...ant 0 99 min 2 dFd Temperature displayed during defrost rt real temperature it temperature at defrost start SEt set point dEF dEF label 2 dAd MAX display delay after defrost Sets the maximum time betw...

Page 14: ...the SET A LU or SET ALL values 2 ALU Maximum temperature alarm when this temperature is reached the alarm is enabled after the ALd delay time SET 110 C SET 230 F 2 ALL Minimum temperature alarm when...

Page 15: ...pressure switch dur ing the did interval before signalling the alarm event I2F PAL If the nPS activation in the did time is reached switch off and on the instru ment to restart normal regulation 0 15...

Page 16: ...neutral zone n n n y in case of heating kit 2 AC Anti short cycle delay 1 1 1 2 CCt Continuous cycle duration 0 0 0 2 CCS Set point for continuous cycle 0 0 0 2 COn Compressor ON time with faulty pro...

Page 17: ...2 ALd Temperature alarm delay 15 15 15 2 dAo Delay of temperature alarm at start up 1 3 1 3 1 3 2 SE Regular service has to be performed x10 hours 200 200 200 2 10 4 6 Digital input Label Description...

Page 18: ...tt oder der Webseite Ihrer jeweiligen Webasto Landesvertretung Dans le cas d une version r dig e en plusieurs langues l anglais est alors la langue qui fait foi Pour trouver le num ro de t l phone du...

Reviews: