Webasto Frigo Top 10 Workshop Manual Download Page 12

Frigo Top 10 - 43 | Pordoi 2000 - 4000 12 

10.3  Parameter description

10.3.1 Regulation

Label Description

Range

Program level

2

HY

Intervention differential for set point: 
Compressor Cut IN is Set Point Plus Differential (HY). 
Compressor Cut OUT is when the temperature reaches the set point.

0.1 – 25.5 °C (1 – 255 °F)

2

LS

Minimum set point: 
Sets the minimum acceptable value for the set point.

- 50 °C – SET (-58 °F – SET)

1

US

Maximum set point: 
Sets the maximum acceptable value for set point.

SET – 110 °C (SET – 230 °F)

1

ot

Thermostat probe calibration: allows to adjust the possible offset of the 
thermostat probe.

-12 – 12 °C (-120 – 120 °F)

2

P2P

Evaporator probe presence: 
n = not present: time stops the defrost cycle; 
y = present: temperature stops the defrost cycle.

1

oE

Evaporator probe calibration: 
Allows to adjust possible offset of the evaporator probe.

-12 – 12 °C (-120 – 120 °F).

2

odS

Outputs activation delay at start up:  
This function is enabled at the initial start up of the instrument and inhibits 
any output activation for the period of time set in the parameter.

0 – 255 min

2

db

Dead band (= neutral zone); allows the system to control the cell tempera-
ture to higher or lower temeratures compared to the set temperature. To 
be used in case of heating kit.
n = neutral zone disabled; cooling only 
y = neutral zone enabled; heating kit installed

2

AC

Anti-short cycle delay: minimum interval between the compressor stop and 
the following restart.

0 – 50 min

2

CCt

Compressor ON time during continuous cycle: 
Allows to set the length of the continuous cycle: compressor stays on with-
out interruption for the CCt time. Can be used, for instance, when the room 
is filled with new products.

0.0 – 24.0 h; res. 10 min

2

CCS

Set point for continuous cycle: it sets the set point used during the continu-
ous cycle. 

-50 – 150 °C (-58 – 302 °F)

2

Con

Compressor ON time with faulty probe: time during which the compressor 
is active in case of faulty thermostat probe. 
With Con = 0 the compressor is always OFF.

0 – 255 min

2

CoF

Compressor OFF time with faulty probe: time during which the compressor 
is OFF in case of faulty thermostat probe. 
With COF = 0 the compressor is always active.

0 – 255 min

2

10.3.2 Display

Label Description

Range

Program level

1

2

CF

Temperature measurement unit: 
°C = Celsius; °F = Fahrenheit. 

ATTENTION

When the measurement unit is changed the SET point and the 
values of the parameters HY, LS, US, Ot, ALU and ALL have to 
be checked and modified if necessary).

2

rES

Display resolution (for °C only): 
in = 1 °C; 
dE = 0.1 °C; allows decimal point display.

2

Summary of Contents for Frigo Top 10

Page 1: ...Workshop Manual Transport Refrigeration Frigo Top 10 43 Pordoi 2000 4000 English F...

Page 2: ...vel menus 6 4 1 Entering the 1st service level 6 4 2 Entering the 2nd service level 6 4 3 Change a parameter setting 6 4 4 Exit a service menu 6 5 Set and reset the service interval 7 5 1 Enter the se...

Page 3: ...l Result damage to the refrigeration system X X Follow the operating instructions and instructions described in this document 2 Safety 2 1 General safety The repair and commissioning personnel must ha...

Page 4: ...compartment 3 3 Service levels The control element has an extensive set of parameters to regu late and control the refrigeration process The parameters are split in 2 levels Level 1 Level 2 Access th...

Page 5: ...pressor operation count appears on the display preceded by a minus sign Example If the saved value is 1511 hours of operation the first time the button is pressed 001 thousands is displayed The second...

Page 6: ...irst parameter of the 1st service level The degree symbol starts blinking 4 2 Entering the 2nd service level Fig 06 2nd level service menu Fig 07 First parameter of the 2nd level service menu X XPress...

Page 7: ...ween SEr change interval rSt reset interval 5 3 Reset the service interval Fig 14 Reset interval No Fig 15 Reset interval Yes 3 3 Make sure that the screen shows rSt ATTENTION Do not reset the service...

Page 8: ...eters from the hot key into the control element Upload parameters from the control element into the hot key Uploading parameters from the control element into the hot key provides a back up for eventu...

Page 9: ...t restarts and uses the new parameters X XRemove the hot key 6 3 Upload parameters to the hot key 3 3 Program the control element as desired with the keys on the front 3 3 Leave the control element on...

Page 10: ...ng the sensor X XContact a Webasto service partner HA Maximum temperature alarm Temperature in cooling compartment is too high LA Minimum temperature alarm Temperature in cooling compartment is too lo...

Page 11: ...input Potential free contact NTC probe 40 110 C 40 230 F Relay outputs PTC probe 50 150 C 58 302 F Compressor 8 3 A 16 6 A or 20 8 A 250 VAC Defrost 8 3 A 250 VAC Fan 8 3 250 VAC Fig 23 F 32 74 71 29...

Page 12: ...emeratures compared to the set temperature To be used in case of heating kit n neutral zone disabled cooling only y neutral zone enabled heating kit installed 2 AC Anti short cycle delay minimum inter...

Page 13: ...ant 0 99 min 2 dFd Temperature displayed during defrost rt real temperature it temperature at defrost start SEt set point dEF dEF label 2 dAd MAX display delay after defrost Sets the maximum time betw...

Page 14: ...the SET A LU or SET ALL values 2 ALU Maximum temperature alarm when this temperature is reached the alarm is enabled after the ALd delay time SET 110 C SET 230 F 2 ALL Minimum temperature alarm when...

Page 15: ...pressure switch dur ing the did interval before signalling the alarm event I2F PAL If the nPS activation in the did time is reached switch off and on the instru ment to restart normal regulation 0 15...

Page 16: ...neutral zone n n n y in case of heating kit 2 AC Anti short cycle delay 1 1 1 2 CCt Continuous cycle duration 0 0 0 2 CCS Set point for continuous cycle 0 0 0 2 COn Compressor ON time with faulty pro...

Page 17: ...2 ALd Temperature alarm delay 15 15 15 2 dAo Delay of temperature alarm at start up 1 3 1 3 1 3 2 SE Regular service has to be performed x10 hours 200 200 200 2 10 4 6 Digital input Label Description...

Page 18: ...tt oder der Webseite Ihrer jeweiligen Webasto Landesvertretung Dans le cas d une version r dig e en plusieurs langues l anglais est alors la langue qui fait foi Pour trouver le num ro de t l phone du...

Reviews: