Webasto Frigo Top 10 Workshop Manual Download Page 13

Frigo Top 10 - 43 | Pordoi 2000 - 4000 13 

Label Description

Range

Program level

1

2

Lod

Instrument display : selects which probe is displayed by the instrument: 
P1 = Thermostat probe; 
P2 = Evaporator probe.

2

10.3.3 Defrost

Label Description

Range

Program level

1

2

tdF

Defrost type: 
EL = electrical heater; 
in = hot gas

2

dtE

Defrost termination temperature: (Enabled only when EdF = Pb).
Sets the temperature measured by the evaporator probe, which causes the 
end of defrost.

-50 – 50 °C (-58 – 122 °F)

1

idF

Interval between defrost cycles: 
Determines the time interval between the beginning of two defrost cycles.

0 – 120 h

1

MdF

(Maximum) length for defrost: 
When P2P = n, (no evaporator probe: timed defrost) it sets the defrost du-
ration, 
when P2P = y, (defrost end based on temperature) it sets the maximum 
length for defrost.

0 – 255 min

1

dSd

Start defrost delay: 
This is useful when different defrost start times are necessary to avoid over-
loading the plant.

0 – 99 min

2

dFd

Temperature displayed during defrost:  
rt = real temperature; 
it = temperature at defrost start; 
SEt = set point; 
dEF = “dEF” label

2

dAd

MAX display delay after defrost: 
Sets the maximum time between the end of defrost and the restarting of 
the real room temperature display.

0 – 255 min

2

Fdt

Drip time: time interval between reaching defrost termination temperature 
and the restoring of the control’s normal operation. This time allows the 
evaporator to eliminate water drops that might have formed due to de-
frost.

0 – 120 min

1

dPo

First defrost after start-up: 
y = immediately;  
n = after the IdF time

2

dAF

Defrost delay after continuous cycle: time interval between the end of the 
fast freezing cycle and the following defrost related to it.

0 – 23.5 h

2

10.3.4 Fans

Label Description

Range

Programm level

1

2

FnC

Fans operating mode: 
C-n = runs with the compressor, OFF during defrost; 
o-n = continuous mode, OFF during defrost; 
C-Y = runs with the compressor, ON during defrost; 
o-Y = continuous mode, ON during defrost;

1

Fnd

Fans delay after defrost: Time interval between end of defrost and evapora-
tor fans start.

0 – 255 min

2

Summary of Contents for Frigo Top 10

Page 1: ...Workshop Manual Transport Refrigeration Frigo Top 10 43 Pordoi 2000 4000 English F...

Page 2: ...vel menus 6 4 1 Entering the 1st service level 6 4 2 Entering the 2nd service level 6 4 3 Change a parameter setting 6 4 4 Exit a service menu 6 5 Set and reset the service interval 7 5 1 Enter the se...

Page 3: ...l Result damage to the refrigeration system X X Follow the operating instructions and instructions described in this document 2 Safety 2 1 General safety The repair and commissioning personnel must ha...

Page 4: ...compartment 3 3 Service levels The control element has an extensive set of parameters to regu late and control the refrigeration process The parameters are split in 2 levels Level 1 Level 2 Access th...

Page 5: ...pressor operation count appears on the display preceded by a minus sign Example If the saved value is 1511 hours of operation the first time the button is pressed 001 thousands is displayed The second...

Page 6: ...irst parameter of the 1st service level The degree symbol starts blinking 4 2 Entering the 2nd service level Fig 06 2nd level service menu Fig 07 First parameter of the 2nd level service menu X XPress...

Page 7: ...ween SEr change interval rSt reset interval 5 3 Reset the service interval Fig 14 Reset interval No Fig 15 Reset interval Yes 3 3 Make sure that the screen shows rSt ATTENTION Do not reset the service...

Page 8: ...eters from the hot key into the control element Upload parameters from the control element into the hot key Uploading parameters from the control element into the hot key provides a back up for eventu...

Page 9: ...t restarts and uses the new parameters X XRemove the hot key 6 3 Upload parameters to the hot key 3 3 Program the control element as desired with the keys on the front 3 3 Leave the control element on...

Page 10: ...ng the sensor X XContact a Webasto service partner HA Maximum temperature alarm Temperature in cooling compartment is too high LA Minimum temperature alarm Temperature in cooling compartment is too lo...

Page 11: ...input Potential free contact NTC probe 40 110 C 40 230 F Relay outputs PTC probe 50 150 C 58 302 F Compressor 8 3 A 16 6 A or 20 8 A 250 VAC Defrost 8 3 A 250 VAC Fan 8 3 250 VAC Fig 23 F 32 74 71 29...

Page 12: ...emeratures compared to the set temperature To be used in case of heating kit n neutral zone disabled cooling only y neutral zone enabled heating kit installed 2 AC Anti short cycle delay minimum inter...

Page 13: ...ant 0 99 min 2 dFd Temperature displayed during defrost rt real temperature it temperature at defrost start SEt set point dEF dEF label 2 dAd MAX display delay after defrost Sets the maximum time betw...

Page 14: ...the SET A LU or SET ALL values 2 ALU Maximum temperature alarm when this temperature is reached the alarm is enabled after the ALd delay time SET 110 C SET 230 F 2 ALL Minimum temperature alarm when...

Page 15: ...pressure switch dur ing the did interval before signalling the alarm event I2F PAL If the nPS activation in the did time is reached switch off and on the instru ment to restart normal regulation 0 15...

Page 16: ...neutral zone n n n y in case of heating kit 2 AC Anti short cycle delay 1 1 1 2 CCt Continuous cycle duration 0 0 0 2 CCS Set point for continuous cycle 0 0 0 2 COn Compressor ON time with faulty pro...

Page 17: ...2 ALd Temperature alarm delay 15 15 15 2 dAo Delay of temperature alarm at start up 1 3 1 3 1 3 2 SE Regular service has to be performed x10 hours 200 200 200 2 10 4 6 Digital input Label Description...

Page 18: ...tt oder der Webseite Ihrer jeweiligen Webasto Landesvertretung Dans le cas d une version r dig e en plusieurs langues l anglais est alors la langue qui fait foi Pour trouver le num ro de t l phone du...

Reviews: