background image

7

www.waynepumps.com

CWS Series

INSTALLATION (CONTINUED)

5.  Slope the horizontal pipes upward toward the pump to prevent 

trapping air. If horizontal distance exceeds 25 feet, see Chart 1 for 
recommended pipe sizes.

DRILLED WELL (2 IN.) WITH SINGLE PIPE PACKER (FIGURES 16 
AND 4)

NOTE:

 Single pipe packer jets rely on the space between single pipe and 

inside of well casing for return water to operate jet. Two inch installations 
must use 1-1/4 in. galvanized steel pipe with special turned couplings (1-
13/16 in. O.D.) to avoid restricting flow of return water back to jet.
1.  Assemble the foot valve and packer to the jet body.
2.  Lubricate the rubber cups with petroleum jelly.
3.  Attach the first section of pipe and lower jet into well.
4.  Add pipe until the jet is positioned 5 - 15 feet below the lowest 

anticipated water level. The jet should never be closer than 5 feet 
from the bottom of the well or sand and sediment may be drawn 
into the system.

5.  With the jet in position, fill the pipes with water to make sure the 

rubber cups are sealed against inside of the well casing. It may be 
necessary to move the jet up and down to seat the cups.

6.  Install the casing adapter and the horizontal pipes.
7.  Slope both pipes upward toward the pump to eliminate trapping air. 

If the horizontal distance exceeds 25 feet, see Chart 1 below, for the 
recommended pipe sizes.

CHART 1 - PIPE SIZING

Pump Model

Pump 

Opening

Horizontal Distance 

(Feet)

0-25

26-100

Deep Well

Inlet: Suction

1-1/4 in.

1-1/2 in.

Inlet: Drive

1 in.

1-1/4 in.

Outlet

3/4 in.

1 in.

DEEP WELL PUMP WITH HORIZONTAL AND VERTICAL 
STORAGE TANK (FIGURES 5 AND 6)

1.  Install the air volume control on the tank as shown.

1-1/4 IN. PIPE

Figure 4 - Single Pipe Jet (2” Casing)

PACKER

FOOT VALVE

CUPS

2.  Connect the copper tube from the air volume control to the 1/8 in. 

NPT opening directly above the 1-1/4 in. opening on the front of the 

pump.

3.  Install a valve and isolating hose between the system and the house 

plumbing to aid in pump removal for servicing and for reducing noise 

transmitted through the house piping.

4.  Provide a faucet at the lowest point in the system to drain for service 

or storage.

Figure 5 - Horizontal Tank

AIR 
VOLUME 
CONTROL 
TUBING

OUTLET

AIR 

VOLUME 

CONTROL

PRESSURE SWITCH

PRIME PLUG

TO JET 
ASSEMBLY

CONVENTIONAL TANK

PUMP

Summary of Contents for CWS Series

Page 1: ...56 948 846 750 642 516 384 294 234 180 40 840 750 642 528 384 294 234 180 126 72 50 588 444 330 264 234 180 126 72 CWS75 3 4 30 990 906 774 630 510 408 306 246 186 54 40 780 630 510 408 306 246 186 11...

Page 2: ...qui si elle n est pas vit e pourrait entra ner des blessures mineures ou mod r es Notice indicates important information that if not followed may cause damage to equipment This is the safety alert sy...

Page 3: ...on annuler la garantie All wiring should be performed by a licensed or certified electrician Tout c blage doit tre r alis par un lectricien agr ou certifi 10 Make sure the line voltage and frequency o...

Page 4: ...LLATION LOCATION Select a location as close to the water supply as possible Be sure to comply with any state or local codes regarding the placement of the pump The equipment must be protected from the...

Page 5: ...ng air Sloping the pipe will also aid in priming the pump DRIVEN WELL FIGURE 16 PAGE 13 Drive the point several feet below the water table NOTE A packer type foot valve can be installed in the well Fi...

Page 6: ...tall the horizontal pipe from the well to the pump Piping from the vertical well pipe to the pump should never be smaller than the well pipes 7 Slope both pipes upward toward the pump to prevent trapp...

Page 7: ...ainst inside of the well casing It may be necessary to move the jet up and down to seat the cups 6 Install the casing adapter and the horizontal pipes 7 Slope both pipes upward toward the pump to elim...

Page 8: ...etween the system and the house plumbing to aid in pump removal for servicing and for reducing noise transmitted to the house through the piping 4 Provide a faucet at the lowest point in the system to...

Page 9: ...round connection must be made at this terminal Figure 9 The ground conductor must not be smaller than the circuit conductors supplying the motor The voltage of power supply must match the voltage of t...

Page 10: ...endommager la pompe ne pas d marrer le moteur tant que la pompe n a pas t remplie d eau 1 Remove prime plug 2 Fill pump and piping completely full of water 3 Replace the prime plug 4 Close the contro...

Page 11: ...ssurized water in the system 3 Prime the pump See Priming the Shallow Well or Priming the Deep Well Sections 4 Reconnect the power to the pump NOTE As the pump refills the tank with water the air volu...

Page 12: ...be orientated during assembly so the two holes are on a horizontal line across the motor shaft Figure 14 18 Push the bellows side of the shaft seal over the impeller hub you can use a little water or...

Page 13: ...or concrete to prevent cave in D DRIVEN WELL Pipe with a pointed screen is driven into the ground below the water table The depth is usually less than 50 feet Available diameters are 1 through 2 E DR...

Page 14: ...d 5 Well screen or inlet strainer clogged 5 Clean or replace as necessary 6 Clogged nozzle deep well 6 Pull jet and clear obstruction 7 Air volume control diaphragm ruptured 7 Replace air volume contr...

Page 15: ...Harrison OH 45030 U S A 1 REPLACEMENT PARTS Ref No Description Models Qty CWS50 CWS75 CWS100 1 2 Square Ring Gaskets Impeller Jet Pump Dissfuser and Shaft Seal Assembly 64046 WYN1 CWS50 64047 WYN1 CW...

Page 16: ...DING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE AND ANY RIGHTS OR REMEDIES AGAINST ANY PERSON OR ENTITY UNDER THE UNIFORM COMMERCIAL CODE OR OTHERWISE WITH RESPECT T...

Reviews: