background image

11

www.waynepumps.com

CWS Series

MAINTENANCE

 

Disconnect power and release all pressure from 

  the system before attempting to install, service, 

relocate or perform any maintenance. Lock the power disconnect in the 

open (off) position. Tag out the power disconnect to prevent unexpected 

application of power.
 

Débrancher de la source d’alimentation puis  

 

  dissiper toute la pression du système avant 

d’essayer d’installer, de réparer, de déplacer ou de procéder à l’entretien. 

Verrouiller le sectionneur de courant en position ouverte (OFF). Étiqueter le 
sectionneur de courant pour éviter toute mise sous tension imprévue.

 

 

Protect the pump from freezing during winter 

 conditions.

 MISE EN GARDE

 

        Protéger la pompe du gel pendant l’hiver.

DRAINING THE PUMP

Drain openings are provided on all models. To drain the pump:
1.  Remove drain plug and prime plug to vent the system.
2.  Drain all piping to a point below the freeze line.

DRAINING THE TANK

Conventional tanks can be drained by opening an outlet at the lowest 
point in the system. Remove plug or the air volume control to vent the 
tank.
Pre-charged tanks force virtually all the water from the tank when system 
pressure is released. No draining is necessary.

RESTARTING PUMP

If the pump has been serviced, drained or has not been used for some 
time, be sure there is water in the pump housing (volute) and the piping 
to the well. There must be water in the pump housing (volute) at all times 
when the pump is running to avoid internal damage of seal members 
(See Priming the Shallow Well or Priming the Deep Well Sections).

WATERLOGGED TANKS: CONVENTIONAL

When a tank system has an inadequate ratio of air and water, the pump 
will start and stop often and erratically.
1.  Disconnect the power to the pump.
2.  Open the lowest faucet in the system to release all pressurized water 

in the system.

3.  Prime the pump (See Priming the Shallow Well or Priming the Deep 

Well Sections).

4.  Reconnect the power to the pump.

NOTE:

 As the pump refills the tank with water, the air volume control 

supplies the tank with the correct air to water ratio for the system to 
operate. If the air volume control is good, the pump will shut off at the 
desired cut-off and will be adjusted correctly.

WATERLOGGED TANKS: PRE-CHARGED

If a pre-charged tank becomes waterlogged, the bladder is normally 
leaking or broken.
1.  Test the tank by depressing the air valve. The air valve will expel 

water if the bladder is broken.

2.  Replace the tank.

NOTE:

 Once an internal bladder is leaking or broken, the bladder cannot 

be repaired. The tank must be replaced.

PRE-CHARGED TANK

Some air is lost through the internal bladder in any tank. To prevent tank 
failure, check the tank pre-charge on a yearly basis.
1.  Disconnect power to the pump
2.  Open a faucet nearest the tank and allow all water to drain from the 

tank.

3.  Measure the tank pre-charge at the valve stem using a tire gauge.
4.  If necessary, adjust the pre-charge with an air pump 28 - 30 psi on 

1/2, 3/4 and 1 HP pumps.

LUBRICATION

The bearing used in the pumps are lifetime lubricated at the factory and 
require no additional lubrication. 

CWS REPAIR KIT

1.  Disconnect power from the pump.
2.  Open faucet nearest the tank and allow all of the water to drain from 

the tank and pump.

3.  Remove 4 cap screws holding pump housing, do not disconnect 

pressure switch (Figure 12).

4.  Remove pump housing from pump assembly, move it out of the 

way.

5.  Using a 5/16” socket or flat blade screw drive remove the 2 screws 

from the diffuser on the pump assembly.

6.  Remove the diffuser.
7.  Remove the black plastic cap from the back of the motor, exposing 

the motor shaft end. 

8.  Using a large flat bladed screw driver hold the motor shaft while 

unscrewing the impeller.

9.  Remove the seal plate. Pay attention to how the original shaft seal is 

installed before disassembly.

Summary of Contents for CWS Series

Page 1: ...56 948 846 750 642 516 384 294 234 180 40 840 750 642 528 384 294 234 180 126 72 50 588 444 330 264 234 180 126 72 CWS75 3 4 30 990 906 774 630 510 408 306 246 186 54 40 780 630 510 408 306 246 186 11...

Page 2: ...qui si elle n est pas vit e pourrait entra ner des blessures mineures ou mod r es Notice indicates important information that if not followed may cause damage to equipment This is the safety alert sy...

Page 3: ...on annuler la garantie All wiring should be performed by a licensed or certified electrician Tout c blage doit tre r alis par un lectricien agr ou certifi 10 Make sure the line voltage and frequency o...

Page 4: ...LLATION LOCATION Select a location as close to the water supply as possible Be sure to comply with any state or local codes regarding the placement of the pump The equipment must be protected from the...

Page 5: ...ng air Sloping the pipe will also aid in priming the pump DRIVEN WELL FIGURE 16 PAGE 13 Drive the point several feet below the water table NOTE A packer type foot valve can be installed in the well Fi...

Page 6: ...tall the horizontal pipe from the well to the pump Piping from the vertical well pipe to the pump should never be smaller than the well pipes 7 Slope both pipes upward toward the pump to prevent trapp...

Page 7: ...ainst inside of the well casing It may be necessary to move the jet up and down to seat the cups 6 Install the casing adapter and the horizontal pipes 7 Slope both pipes upward toward the pump to elim...

Page 8: ...etween the system and the house plumbing to aid in pump removal for servicing and for reducing noise transmitted to the house through the piping 4 Provide a faucet at the lowest point in the system to...

Page 9: ...round connection must be made at this terminal Figure 9 The ground conductor must not be smaller than the circuit conductors supplying the motor The voltage of power supply must match the voltage of t...

Page 10: ...endommager la pompe ne pas d marrer le moteur tant que la pompe n a pas t remplie d eau 1 Remove prime plug 2 Fill pump and piping completely full of water 3 Replace the prime plug 4 Close the contro...

Page 11: ...ssurized water in the system 3 Prime the pump See Priming the Shallow Well or Priming the Deep Well Sections 4 Reconnect the power to the pump NOTE As the pump refills the tank with water the air volu...

Page 12: ...be orientated during assembly so the two holes are on a horizontal line across the motor shaft Figure 14 18 Push the bellows side of the shaft seal over the impeller hub you can use a little water or...

Page 13: ...or concrete to prevent cave in D DRIVEN WELL Pipe with a pointed screen is driven into the ground below the water table The depth is usually less than 50 feet Available diameters are 1 through 2 E DR...

Page 14: ...d 5 Well screen or inlet strainer clogged 5 Clean or replace as necessary 6 Clogged nozzle deep well 6 Pull jet and clear obstruction 7 Air volume control diaphragm ruptured 7 Replace air volume contr...

Page 15: ...Harrison OH 45030 U S A 1 REPLACEMENT PARTS Ref No Description Models Qty CWS50 CWS75 CWS100 1 2 Square Ring Gaskets Impeller Jet Pump Dissfuser and Shaft Seal Assembly 64046 WYN1 CWS50 64047 WYN1 CW...

Page 16: ...DING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE AND ANY RIGHTS OR REMEDIES AGAINST ANY PERSON OR ENTITY UNDER THE UNIFORM COMMERCIAL CODE OR OTHERWISE WITH RESPECT T...

Reviews: