background image

10

www.waynepumps.com

Operating Instructions and Parts Manual

OPERATION (CONTINUED) 

L2

3

L1

1

Figure 9 - Electrical Connections

MOTOR

LINE

GROUND 

SCREW

Figure 10 - Voltage Selector

230 V

115 V

4.  Open a faucet to vent the system.
5.  Start the motor. Water will pump in a few minutes. If pump fails to 

prime in 5 minutes, stop motor and refill pump with water. Priming 
time is proportional to the amount of air in inlet pipe. Do not allow 
pump to get hot.

6.  Let the system operate for several minutes to flush all pipes.
7.  Close faucet and allow pump to build pressure in tank. When the 

pressure reaches the cut-out setting, the motor will stop.

The system is now in operation and will automatically cycle on demand.

 PRIMING THE DEEP WELL PUMP

  To prevent damage to the pump, do not start 

motor until pump has been filled with water.

  Pour éviter d’endommager la pompe, ne pas 

démarrer le moteur tant que la pompe n’a pas été remplie d’eau.  

1.  Remove prime plug.
2.  Fill pump and piping completely full of water.
3.  Replace the prime plug.
4.  Close the control valve (Figure 11) and open a nearby faucet.
5.  Start the motor. The pressure inside the pump body will build almost 

immediately as the pump, jet and piping become completely filled 
with water.

6.  Slowly open the control valve. Water will begin to flow. Continue to 

open the control valve until maximum flow is achieved. Opening the 
valve too far will cause the water to stop flowing.

Figure 11 - Control Valve

OPEN

1/4 IN. TURN

CLOSED

7.  Adjust the valve until there is a steady flow of water. The valve should 

be opened as much as possible without losing pressure.

8.  Let the system operate for several minutes to flush all piping.
9.  Close the faucets and allow the pump to build pressure in the tank. 

When the pressure reaches the cut-out setting, the motor will stop.

The system is now in operation and will automatically cycle upon 
demand.

Summary of Contents for CWS Series

Page 1: ...56 948 846 750 642 516 384 294 234 180 40 840 750 642 528 384 294 234 180 126 72 50 588 444 330 264 234 180 126 72 CWS75 3 4 30 990 906 774 630 510 408 306 246 186 54 40 780 630 510 408 306 246 186 11...

Page 2: ...qui si elle n est pas vit e pourrait entra ner des blessures mineures ou mod r es Notice indicates important information that if not followed may cause damage to equipment This is the safety alert sy...

Page 3: ...on annuler la garantie All wiring should be performed by a licensed or certified electrician Tout c blage doit tre r alis par un lectricien agr ou certifi 10 Make sure the line voltage and frequency o...

Page 4: ...LLATION LOCATION Select a location as close to the water supply as possible Be sure to comply with any state or local codes regarding the placement of the pump The equipment must be protected from the...

Page 5: ...ng air Sloping the pipe will also aid in priming the pump DRIVEN WELL FIGURE 16 PAGE 13 Drive the point several feet below the water table NOTE A packer type foot valve can be installed in the well Fi...

Page 6: ...tall the horizontal pipe from the well to the pump Piping from the vertical well pipe to the pump should never be smaller than the well pipes 7 Slope both pipes upward toward the pump to prevent trapp...

Page 7: ...ainst inside of the well casing It may be necessary to move the jet up and down to seat the cups 6 Install the casing adapter and the horizontal pipes 7 Slope both pipes upward toward the pump to elim...

Page 8: ...etween the system and the house plumbing to aid in pump removal for servicing and for reducing noise transmitted to the house through the piping 4 Provide a faucet at the lowest point in the system to...

Page 9: ...round connection must be made at this terminal Figure 9 The ground conductor must not be smaller than the circuit conductors supplying the motor The voltage of power supply must match the voltage of t...

Page 10: ...endommager la pompe ne pas d marrer le moteur tant que la pompe n a pas t remplie d eau 1 Remove prime plug 2 Fill pump and piping completely full of water 3 Replace the prime plug 4 Close the contro...

Page 11: ...ssurized water in the system 3 Prime the pump See Priming the Shallow Well or Priming the Deep Well Sections 4 Reconnect the power to the pump NOTE As the pump refills the tank with water the air volu...

Page 12: ...be orientated during assembly so the two holes are on a horizontal line across the motor shaft Figure 14 18 Push the bellows side of the shaft seal over the impeller hub you can use a little water or...

Page 13: ...or concrete to prevent cave in D DRIVEN WELL Pipe with a pointed screen is driven into the ground below the water table The depth is usually less than 50 feet Available diameters are 1 through 2 E DR...

Page 14: ...d 5 Well screen or inlet strainer clogged 5 Clean or replace as necessary 6 Clogged nozzle deep well 6 Pull jet and clear obstruction 7 Air volume control diaphragm ruptured 7 Replace air volume contr...

Page 15: ...Harrison OH 45030 U S A 1 REPLACEMENT PARTS Ref No Description Models Qty CWS50 CWS75 CWS100 1 2 Square Ring Gaskets Impeller Jet Pump Dissfuser and Shaft Seal Assembly 64046 WYN1 CWS50 64047 WYN1 CW...

Page 16: ...DING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE AND ANY RIGHTS OR REMEDIES AGAINST ANY PERSON OR ENTITY UNDER THE UNIFORM COMMERCIAL CODE OR OTHERWISE WITH RESPECT T...

Reviews: