INSTALLATION MANUAL

8.  Drill 1/8 in. “weep” hole in the discharge pipe 1 in. above 

the pump discharge. Water stream will be visible from 
the how when the pump is running. The hole must be 
cleaned periodically. 

9.  Install a union to allow for easy removal of the pump for 

cleaning or service.

10.  Install a check valve (required) to prevent back-fl ow.  The 

check valve may be positioned just above the basin to 
allow easy removal of the pump for cleaning and service.

11. Install a gate valve or ball valve if required by local, 

regional or state code.

12.  Secure cords to discharge pipe to prevent possible 

switch entanglement. Use cable or zip ties to secure the 
power cords. 

13.  Connect pump power supply cord to a properly 

grounded receptacle.

14.  Fill the basin with water.  The pump will start when the 

water level has reached the switch-on level.

15.  The pump will stop when the water level has reached the 

switch-off level.

16.  Verify the switch is operating with out any obstruction 

from the pump, piping and basin.

17.  Fill the basin with water again.  While the pump is 

draining the basin, verify the discharge pipe is carrying 
the water to a point at least 3 ft. away from the 
foundation.  If the discharge line is exposed to freezing 
temperatures, the pipe must be positions in a downward 
slope away from the foundation so any remaining water 
will drain away and not freeze.

3

TYPICAL SUMP INSTALLATION

1.  This installation must be in accordance with the National 

Electric Code and all applicable local codes and 
ordinances.

2.  Use a basin that is large enough to accommodate the pump. 

The minimum requirements for the sump pumps are:

CHART — A

Switch Type

A

Minimum

 Basin Diameter

B

Minimum 

Basin Height

Submersible Sumps

Tether Float Switch

14 in.

22 in.

Diaphragm Switch 

14 in.

22 in.

Vertical Float Switch

11 in.

22 in.

iSwitch Technology Switch

11 in.

22 in.

CHART — B

Switch Type

A

Minimum 

Basin Diameter

B

Maximum 

Basin Height

Pedestal Float Switch

(Figure 2)

14 in.

22 in.

3.  Clean the basin of all debris. Position pump so the switch 

is away from the inlet and is clear from incoming water.

4.  Assemble switch or fl oat if needed.  Refer to 

warranty 

and service

 

parts sheet 

for specifi c directions.

5.  Set the pump on a solid, level surface.  Do not place pump 

directly on clay, earth, gravel or sand.  A brick or block may 
be installed under the pump to provide a solid base.

6.  Position pump so the switch is away from the inlet so 

switch is clear from incoming water. Verify the switch 
has at least 1 in. clearance to the side wall of the 
basin and is free to move throughout its movement. If 
optional control device or fl oat is used, follow mounting 
instruction supplied with device or fl oat.

7.  Install discharge plumbing according to local, regional 

and state codes.  Rigid PVC pipe is recommended. 

Printed on 100% Recycled Paper

Summary of Contents for 200000-015

Page 1: ...ected with a ground fault circuit interrupter GFCI All wiring must be performed by a qualified licensed electrician and comply with the National Electric Code and all applicable local codes and ordina...

Page 2: ...debris that could interfere with the operation of the switch IT IS RECOMMENDED TO USE A CHECK VALVE with this pump to prevent the back flow of fluid after each pump cycle DO NOT INSTALL OR OPERATE TH...

Page 3: ...undation so any remaining water will drain away and not freeze 3 TYPICAL SUMP INSTALLATION 1 This installation must be in accordance with the National Electric Code and all applicable local codes and...

Page 4: ...discharge Water stream will be visible from the hole when the pump is running The hole must be cleaned periodically 9 Install a union to allow easy removal of the pump for cleaning and service 10 Ins...

Page 5: ...ng instruction supplied with device or float 9 Install a sealed basin cover to prevent debris from falling into the basin personal injury and contain gases and odors 10 A union should be installed abo...

Page 6: ...protector and may restart unexpectedly Protector tripping is an indication of motor overloading as a result of operating the pump at low heads excessively high or low voltage inadequate wiring incorre...

Page 7: ...g available at local hardware stores to isolate pump vibration from discharge plumbing Pump will not shut off 1 Switch 2 Switch obstructions 3 Restricted discharge obstruction in piping 4 Excessive in...

Page 8: ...8 NOTES INSTALLATION MANUAL Printed on 100 Recycled Paper...

Page 9: ...S CURIT la prise de courant doit tre prot g e avec un disjoncteur de fuite la terre DDFT Tout le c blage doit tre effectu par un lectricien qualifi et se conformer au code national de l lectricit des...

Page 10: ...UTILISER UN CLAPET DE NON RETOUR avec cette pompe pour pr venir le retour d eau de liquide apr s chaque cycle de pompe NE PAS INSTALLER NI FAIRE FONCTIONNER LA POMPE SI ELLE A T ENDOMMAG E DE TOUTE F...

Page 11: ...plac sur une pente vers le bas loin de la fondation pour que l eau restante se draine au lieu de geler 11 INSTALLATION TYPIQUE DE PUISARD 1 Cette installation doit tre conforme au Code national d lect...

Page 12: ...ent 9 Installer un raccord union pour permettre d enlever facilement la pompe pour le nettoyage et l entretien 10 Installer un clapet de non retour requis pour viter tout retour d eau Il doit tre inst...

Page 13: ...cuvette scell e pour emp cher les d bris d y tomber pr venir les blessures et contenir le gaz et les odeurs 10 Un raccord union doit tre install au dessus de la cuvette pour permettre d enlever facil...

Page 14: ...pourrait red marrer de mani re impr vue Le d clenchement du protecteur est une indication de surcharge du moteur suite l op ration de la pompe faible hauteur de chute tension excessivement haute ou ba...

Page 15: ...pas 1 Interrupteur d fectueux 2 Obstruction d interrupteur 3 D charge obstru e obstruction dans la tuyauterie 4 Entr e excessive ou pompe non pas de la taille appropri e pour l application 1 Remplacer...

Page 16: ...16 NOTES MANUEL D INSTALLATION Printed on 100 Recycled Paper...

Page 17: ...URIDAD el tomacorriente debe ser protegido con un interruptor de descarga a tierra GFCI Todo el alambrado debe ser realizado por un electricista autorizado y calificado y debe cumplir con los C digos...

Page 18: ...A EL USO DE UNA V LVULA DE RETENCI N con esta bomba para prevenir el reflujo de l quido despu s de cada ciclo de la bomba NO INSTALE NI HAGA FUNCIONAR LA BOMBA SI HA SIDO DA ADA DE CUALQUIER MANERA NO...

Page 19: ...ientos para que toda agua restante escurra y no se congele 19 INSTALACI N T PICA DE SUMIDERO 1 Esta instalaci n debe realizarse de acuerdo con los C digos el ctricos nacionales y todos los c digos y o...

Page 20: ...jero El agujero debe limpiarse peri dicamente 9 Instale una uni n para facilitar el retiro de la bomba para limpieza y servicio 10 Instale una v lvula de retenci n requerida para prevenir el reflujo D...

Page 21: ...n el dispositivo o flotador 9 Instalan una tapa de pileta con sello para impedir la ca da de residuos en la pileta lesiones personales y para contener gases y olores 10 Debe instalarse una uni n arrib...

Page 22: ...ndica una sobrecarga del motor debido a que la bomba est funcionando con cargas bajas baja restricci n de descarga voltajes excesivamente altos o bajos un cableado inadecuado condiciones incorrectas d...

Page 23: ...l espiral limpie y o reemplace el impulsor La bomba no se apaga 1 Interruptor defectuoso 2 Obstrucci n del interruptor 3 Descarga restringida obstrucci n en la tuber a 4 Demasiado flujo de entrada o l...

Page 24: ...24 NOTAS MANUAL DE INSTALACI N Printed on 100 Recycled Paper...

Reviews: