![Wavetronix click 301 Using Manual Download Page 11](http://html1.mh-extra.com/html/wavetronix/click-301/click-301_using-manual_3881571011.webp)
11 of 13
WX-501-0531 • 01.22
Setting
Description
Disconnect Mode
Allows you to set conditions under which the device should drop a connection.
Ignore DTR
, the default, indicates that the Modem Control In doesn’t affect the
connection.
DTR Drop
sets the network connection to or from the serial port to disconnect (drop)
when Modem Control In transitions from an asserted state to not asserted state.
Start Character
Provides a place to enter the start character that is used to signal the active startup
function (found under the Connect tab) to attempt to connect.
Telnet Mode
Enables Telnet mode.
Port Password
Enables the use of a password on the serial port.
CTRL-D Disconnect
Drops the connection when Ctrl-D or Hex 04 is detected. Both Telnet Com Port Cntrl and
Check EOT (Ctrl+D) must be enabled for Disconnect with EOT to function properly. Ctrl+D
is only detected going from the serial port to the network.
Hard Disconnect
Closes the TCP connection even if the remote site does not acknowledge the disconnect
request.
Inactivity Timeout
Sets the amount of time there can be no activity on the serial line before the device drops
the connection.
Telnet Name/Port Password
Lets you enter either the Telnet name you’re using or the password for the serial port,
depending on which of those two boxes—Telnet Mode or Port Password—is checked.
The
Ethernet > Channel > Packing
tab allows you to configure packing settings, as well as to set other options
(see the figure and table below).
Setting
Description
Packing Algorithm
Enables packing, which defines how long the unit should wait before sending accumulated characters.
Idle Time (ms)
Allows you to set the maximum time for inactivity.
Trailing Chars
Lets you select the number of bytes to send after the end-of-sequence characters. The default is None.
Send Immediate
Causes the module to send immediately after recognizing the transmit condition (sendchar or
timeout). If it is not set, any characters already in the serial buffer are included in the transmission
after a “transmit” condition is found.
Send Char 2-Byte
Causes the device to interpret the sendchars as a 2-byte sequence; if this option is not enabled,
the module interprets them independently.