background image

15 of 23

WX-501-0552 • 01.22

If the Click 111 is successful in communicating with a SmartSensor, it will display the baud rate found, using the 

same Level 2 LED system used in selecting the baud rate (covered in the Baud Rate section and the table below). 

After a short time of displaying the autobaud results, the menu will return to normal operation.

If the autobaud fails, all four Level 2 LEDs will flash once, and then the menu will return to normal operation.

Note. 

If the baud rate of either of the RS-485 buses was configured using the DIP switches (so that parameter is 

set to Hardware mode), the Level 2 LED configuration options for that bus will not be displayed (the LED option 

will never come on). If both RS-485 buses are configured using the DIP switches, the Level 1 LED menu option for 

autobaud will not be displayed (the green LED option will never come on).

Baud Rate (Bus 1 and 2)

The next parameters we’ll talk about allow you to manually set the baud rate of the two RS-485 buses. Bus 1 comes up 

first, with the green and yellow LEDs coming on together; bus 2 comes up second, with the blue LED glowing solid.

Note. 

This parameter can also be changed using the DIP switches or Click Supervisor.

Level 1 LEDs

  

  

  

Baud rate for bus 1

  

  

  

Baud rate for bus 1

Level 2 LEDs

  

  

  

9600 bps (default)

  

  

  

19200 bps

  

  

  

38400 bps

  

  

  

57600 bps

  LED off

  

  

  

Cancel and exit menu

  LED on

 Navigating through the Menu and the Menu Operation Example sections for how to configure this parameter.

Because this parameter can also be set by the DIP switches, you may need to ensure that the DIP switches are 

set to Software configuration mode; if they are set to Hardware, the front panel menu will be able to display but 

not change these settings.

Base Channel

The next parameter on the front panel menu label is the base channel. This can be set independently for the two 

buses. To select this parameter for bus 1, release the push-button when the yellow and blue LEDs both come on 

solid; for bus 2, release the push-button when the green and blue LEDs both come on solid.

Note. 

This parameter can also be changed using the DIP switches or Click Supervisor.

This parameter selects how the Click 111 maps the incoming sensor outputs to the card’s outputs. The setting 

determines the starting sensor channel that will be mapped to the associated bus channel 1 output.

Example. 

If you have this parameter set to 3 for bus 1, then sensor channel 3 will be mapped to output channel 

1 on bus 1. And then the card will count up from there: if the bus has four channels allocated to it, then sensor 

channel 4 will be mapped to output 2, sensor channel 5 will be mapped to output 3, and sensor channel 6 will be 

mapped to output 4.

Summary of Contents for Click 111

Page 1: ...thers 9600 5 6 7 8 1 2 3 4 0 0 0 0 SW 0 0 0 1 1 0 0 1 0 3 0 0 1 1 5 0 1 0 0 7 0 1 0 1 9 0 1 1 0 11 0 1 1 1 13 1 0 0 0 15 5 6 7 8 1 2 3 4 1 0 0 1 17 1 0 1 0 19 1 0 1 1 21 1 1 0 0 23 1 1 0 1 25 1 1 1 0...

Page 2: ...of the device as follows Yellow RD Lights up when the Click 111 is receiving data on any port Green TD Lights up when the device is transmitting data on any port Blue MF This LED indicates whether the...

Page 3: ...put channels will be covered later So as long as one of these options suits your needs for output channels using a single Click 111 as outlined below will work just fine 1 If you re using hardware con...

Page 4: ...vered in the DIP Switches section 2 Insert two cards into the rack 3 Connect a patch cable from one of the RJ 11 jacks labeled Bus 1 on the faceplate of the first Click 111 to the surge protector Clic...

Page 5: ...onnection A6 No connection A7 Fault Status Out A8 No connection A9 DC common A10 No connection A11 DC common A12 Channel 5 normally open A13 No connection A14 DC common A15 Channel 9 normally open A16...

Page 6: ...ing multiple configuration methods and some of them can only be set using one particular method The table below lists how each parameter may be accessed and configured DIP Switch Front Panel Menu Clic...

Page 7: ...to choose between Hardware Software modes If Software mode is selected the parameter must be configured using the front panel menu or Click Supervisor If Hardware mode is selected the parameter can b...

Page 8: ...he front panel menu will be able to display the current setting but not change it If all switches are off down Software mode is selected and only Click Supervisor and the front panel menu will be able...

Page 9: ...the current setting but not change it If all switches are off down Software mode is selected and only Click Supervisor and the front panel menu will be able to both display and change the current set...

Page 10: ...know a bus will not be receiving any data for instance if you re only using one sensor with your Click 111 If a bus is disabled from receiving data then its associated channels will not go into a faul...

Page 11: ...e front panel menu will be able to both display and change the current setting Warning If you don t have switch 1 on flipped up to set it to Hardware mode anything you set on switches 2 and 3 will be...

Page 12: ...bank will be referred to as Level 2 and is used in configuring the menu options Mode Menu RD TD MF PWR 1 2 3 4 Detection 1 4 5 8 9 12 13 16 Note The multicolored LEDs also function as activity status...

Page 13: ...hes As shown above the menu options are displayed on the Level 1 LEDs and the configuration parameters are displayed on the Level 2 LEDs If a configuration parameter has been set using the DIP switche...

Page 14: ...bled Bus 1 Data Enabled Bus 2 Data Disabled Bus 1 Data Disabled Bus 2 Data Enabled Bus 1 2 Data Enabled Default LED off Cancel and exit menu LED on See the Navigating through the Menu and the Menu Ope...

Page 15: ...ud rate for bus 1 Level 2 LEDs 9600 bps default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on Navigating through the Menu and the Menu Operation Example sections for how to configu...

Page 16: ...ey are set to Hardware the front panel menu will be able to display but not change these settings Channel Allocation The next parameter on the front panel menu label is channel allocation To select th...

Page 17: ...an also be changed using the DIP switches or Click Supervisor This parameter lets you choose the polarity of the calls placed by the Click 111 A call can be indicated by either high voltage or low vol...

Page 18: ...d red LEDs come on solid Note This parameter can also be changed using the DIP switches or Click Supervisor This parameter lets you choose whether the device will go into a fault state at all If fault...

Page 19: ...the Navigating through the Menu and the Menu Operation Example sections for how to view this parameter After the Click 111 has reset to factory defaults it will check the DIP switches if any of them a...

Page 20: ...ation about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Setting Description Module Allows you to e...

Page 21: ...e and table below Note These parameters can also be configured using the DIP switches or the front panel menu if in the DIP switches they are set to Hardware mode the parameters will appear grayed out...

Page 22: ...is low or high when the output is asserted Chan Out Polarity Lets you choose the polarity of the output channels whether the voltage is low or high when there is a call on that channel Fault Enable Le...

Page 23: ...ve your settings return to the Select Driver screen and more The Save menu allows you to save your settings Select Save to File to save your settings to a file Selecting this will open a directory box...

Reviews: