background image

after 5 minutes of vacancy): The load turns ON and OFF automatically based on 

occupancy detection. Once turned ON the RH-250 keeps the load ON until no 

motion is detected by any of the related RH-250s for the time delay period. If 

the load is turned OFF manually, automatic-ON is re-enabled when no motion is 

detected for 5 minutes. This prevents the load from being turned ON after it was 

deliberately turned OFF.

Time Delay

The time delay can be selected by the user during set up. It can be adjusted 

to any of these fixed values:15 seconds/5 minutes/15 minutes/30 minutes. We 

recommend that the time delay be the same in all sensors related to the same 

load. This makes it easier to understand the multi-way control operation as well 

as trouble shooting. For additional information on how to adjust it, please read the 

SENSOR ADJUSTMENT & PROGRAMMING section of this installation manual.

Light Level

When the operating mode is set for occupancy sensor, Mode 2 (Auto-ON) this 

feature prevents the sensor from automatically turning the lights ON if there is 

already enough light in the area. 
In a multi-way application, each sensor monitors the light level at it’s location. 

If any sensor related to the load detects motion AND the measured light level in 

that sensor’s area is lower than it’s Light Level setting, the load turns ON.
To adjust the light level, please read the SENSOR ADJUSTMENT & 

PROGRAMMING section of this installation manual.

Coverage Area

The RH-250 has a maximum coverage range 

of 180 degrees and a coverage area of 600 

square feet (56 square meters). The sensor 

must have a clear and unobstructed view 

of the coverage area. Objects blocking the 

sensor’s lens may prevent detection thereby 

causing the light to turn OFF even though 

someone is in the area.

Windows, glass doors, and other 

transparent barriers will obstruct the 

sensor’s view and prevent detection.

INSTALLATION & WIRING

These instructions describe only the 3-way circuit applications. For information 

about other applications, consult technical support. 

WARNING

Disconnect power to the wall switch box by turning OFF  

the circuit breaker or removing the fuse for the circuit before 

installing the RH-250, replacing lamps, or doing any electrical work.

1.   Prepare the switch box.

  After the power is turned OFF at the circuit breaker box, remove the existing 

wall plate and mounting screws. Pull the old switch out from the wall box.

2.   Identify the type of circuit.

  You may connect the RH-250 to a single pole or multi-way circuit. If you are 

unable to clearly identify some or all of the wires mentioned in this manual, 

you should consult with a qualified electrician.

  In a 3-way circuit (see Fig. 2), two traveler wires connect to both switches. 

Another wire provides power from the circuit box to one of the switches. A wire 

connects from one switch to the load. A ground wire may also be connected to 

a ground terminal on the old switches. A neutral wire should also be present in 

both wall boxes.

NEUTRAL

GROUND

LOAD/Common

(power to lamp)

NEUTRAL

GROUND

          HOT/Common

(power from circuit box)

TRAVELER

TRAVELER

Lamp/load

MASTER SWITCH

AUXILIARY SWITCH

Fig. 2: Typical 3-Way Switch Wiring

www.wattstopper.com

25'

(7.6m)

12'

(3.7m)

Fig. 1: Sensor Coverage Area

Summary of Contents for RH-250-W

Page 1: ...oad Lighted Switch To help you locate the RH 250 in a dark room the amber LED illuminates the ON OFF button while the controlled load is OFF When the controlled load is ON the LED is OFF Operating Mod...

Page 2: ...es and a coverage area of 600 square feet 56 square meters The sensor must have a clear and unobstructed view of the coverage area Objects blocking the sensor s lens may prevent detection thereby caus...

Page 3: ...m the circuit in the other wiring box to the white wire on the auxiliary RH 250 Connect the power wire from the circuit box HOT to the black wire on the auxiliary RH 250 and to the TRAVELER 1 wire Con...

Page 4: ...DOOR USE ONLY L L Red LOAD power to lamp or fan GROUND TERMINAL GROUND TERMINAL White NEUTRAL Yellow TRAVELER 2 to RH 253 TRAVELER 1 to RH 250 Black Traveler 1 power via RH 253 RH 253 HOT power from c...

Page 5: ...ing Do not overturn the Time Delay adjustment trimpot Adjusting the Light Level This feature is factory set at maximum so that even the brightest light will not prevent the sensor from turning the loa...

Page 6: ...onds to 30 minutes Check the time delay setting for each RH 250 in your multi way configuration Ensure that all RH 250s have the same time delay setting Ensure that there is no movement within the cov...

Page 7: ...gado manual o autom tico de una o varias cargas hasta una carga por cada RH 250 desde varios lugares Tambi n puede ser conectado hasta con cuatro interruptores moment neos unipolares RH 253 para el co...

Page 8: ...orea el nivel de luz natural en su rea Cualquiera de los sensores que detecte movimiento y que determine que la luz natural es insuficiente encender la carga Para ajustar el Nivel de Luz Natural por f...

Page 9: ...ac nicamente para designar el sensor que esta conectado directamente a la carga controlada Conecte el cable de LINEA o FASE del circuito al cable negro del RH 250 auxiliar y al cable VIAJERO 1 Conect...

Page 10: ...on ctelos en paralelo como se muestra ac RH 250 Rojo Tierra Amarillo Negro Blanco Carga Viajero 2 Linea Fase Neutro Viajero 1 Linea Fase TOP INDOOR USE ONLY RH 253 RH 253 Tierra Viajero 1 Viajero 1 Vi...

Page 11: ...re la perilla de ajuste del Retardo de Apagado Ajuste del Nivel de Luz Natural Esta funci n vendr configurada de f brica a su valor m ximo de tal forma que aun la luz natural m s brillante no evitar q...

Page 12: ...ardo de apagado puede ser configurado desde 15 segundos hasta 30 minutos Corrobore el valor de Retardo de Apagado en cada RH 250 Aseg rese de que todos los RH 250 tienen el mismo valor Aseg rese de qu...

Reviews: