Initial Power-up

There is an initial warm-up 

period. If the sensor is in Mode 2 

“Automatic ON” it may take up to a 

minute before the lights turn ON. 

However, the lights can be turned 

ON/OFF manually by pressing the 

“ON/OFF Button” at any time when 

power is supplied to the unit.

4b.  Wiring one RH-250 and one RH-253 single pole momentary switch 

   for multi-way Manual-ON/OFF single load control.

IMPORTANT: The RH-250 must be installed in the 

wiring wall box that connects to the load.

•  Connect the green or non-insulated (copper) GROUND wire in each wiring box 

to the green terminal on each RH-250 and RH-253.

•  Connect the NEUTRAL wire from the circuit and from the lamp (LOAD) to the 

white wire on the RH-250.

•  Connect the power wire from the circuit box (HOT) to one terminal of the 

RH-253 single pole momentary wall switch and to the TRAVELER 1 wire.

•  Connect the TRAVELER 1 wire coming from the RH-253 wiring box to the black 

wire of the RH-250.

•  Connect the lamp power (LOAD) to the red wire on the RH-250.
•  Connect the TRAVELER 2 wire to the other side of the RH-253 single pole 

momentary wall switch and to the yellow wire of the RH-250.

RH-250

 

TOP

INDO

OR U

SE O

NLY

L

L

Red -> LOAD

(power to lamp 

or fan)

GROUND

TERMINAL

GROUND

TERMINAL

White -> 

NEUTRAL

Yellow-> TRAVELER 2 

               to RH-253

TRAVELER 1

               to RH-250

Black-> Traveler 1

      power via RH-253

RH-253

HOT (power from 

                      circuit box)

TRAVELER 2

   to RH-250

Fig. 6: Step 4b. Sensor orientation and wire connections for 3-way operation 

with an RH-253 momentary wall switch

To wire up to four RH-253 single pole momentary wall switches to one 

RH-250, wire them in parallel as shown in the following wiring diagram.

RH-250

Red

Ground

Yellow

Black

White

Load

Traveler 2

Hot

Neutral

Traveler 1 (Hot)

TOP

INDOOR USE ONLY

RH-253

Ground

RH-253

Ground

Ground

Traveler 2

Traveler 1

Traveler 2

Traveler 1

Traveler 2

Traveler 1

120V/60Hz

Fig. 7: Step 4b. Reference wiring diagram for multi-way operation with RH-253 

momentary wall switches (4 maximum)

5.   Put all the new switches into their wall boxes.

  Position the RH-250 switch(es) with the lens above the ON/OFF button (lens at 

top, ON/OFF button at bottom). Use the captive screws on the mounting strap 

to secure the switches to their wall boxes. 

6.   Restore power to the circuit.

  Turn on the breaker or replace the fuse. 

7.   Make any necessary adjustments.

  See the SENSOR ADJUSTMENT & 

PROGRAMMING section for information. 

8. Install cover plates. 

  Install industry standard decorator wall 

switch cover plate (not included)

www.wattstopper.com

Summary of Contents for RH-250-W

Page 1: ...oad Lighted Switch To help you locate the RH 250 in a dark room the amber LED illuminates the ON OFF button while the controlled load is OFF When the controlled load is ON the LED is OFF Operating Mod...

Page 2: ...es and a coverage area of 600 square feet 56 square meters The sensor must have a clear and unobstructed view of the coverage area Objects blocking the sensor s lens may prevent detection thereby caus...

Page 3: ...m the circuit in the other wiring box to the white wire on the auxiliary RH 250 Connect the power wire from the circuit box HOT to the black wire on the auxiliary RH 250 and to the TRAVELER 1 wire Con...

Page 4: ...DOOR USE ONLY L L Red LOAD power to lamp or fan GROUND TERMINAL GROUND TERMINAL White NEUTRAL Yellow TRAVELER 2 to RH 253 TRAVELER 1 to RH 250 Black Traveler 1 power via RH 253 RH 253 HOT power from c...

Page 5: ...ing Do not overturn the Time Delay adjustment trimpot Adjusting the Light Level This feature is factory set at maximum so that even the brightest light will not prevent the sensor from turning the loa...

Page 6: ...onds to 30 minutes Check the time delay setting for each RH 250 in your multi way configuration Ensure that all RH 250s have the same time delay setting Ensure that there is no movement within the cov...

Page 7: ...gado manual o autom tico de una o varias cargas hasta una carga por cada RH 250 desde varios lugares Tambi n puede ser conectado hasta con cuatro interruptores moment neos unipolares RH 253 para el co...

Page 8: ...orea el nivel de luz natural en su rea Cualquiera de los sensores que detecte movimiento y que determine que la luz natural es insuficiente encender la carga Para ajustar el Nivel de Luz Natural por f...

Page 9: ...ac nicamente para designar el sensor que esta conectado directamente a la carga controlada Conecte el cable de LINEA o FASE del circuito al cable negro del RH 250 auxiliar y al cable VIAJERO 1 Conect...

Page 10: ...on ctelos en paralelo como se muestra ac RH 250 Rojo Tierra Amarillo Negro Blanco Carga Viajero 2 Linea Fase Neutro Viajero 1 Linea Fase TOP INDOOR USE ONLY RH 253 RH 253 Tierra Viajero 1 Viajero 1 Vi...

Page 11: ...re la perilla de ajuste del Retardo de Apagado Ajuste del Nivel de Luz Natural Esta funci n vendr configurada de f brica a su valor m ximo de tal forma que aun la luz natural m s brillante no evitar q...

Page 12: ...ardo de apagado puede ser configurado desde 15 segundos hasta 30 minutos Corrobore el valor de Retardo de Apagado en cada RH 250 Aseg rese de que todos los RH 250 tienen el mismo valor Aseg rese de qu...

Reviews: