TROUBLESHOOTING

Lights do not turn ON with motion (LED does flash)

1. Press and release each button to make sure that the correct lights come

ON for each relay. 

If the lights do NOT turn ON

, check wire connections,

especially the Load connection. 

If the lights turn ON

, verify that the

correct On Mode is selected in DIP switches 8 and 9.

2. Check to see if light level control is enabled: cover the sensor lens with

your hand. If the lights come ON, adjust the light level setting. 

3. If lights still do not turn ON, call 800.879.8585 for technical support.

Lights do not turn ON with motion (LED does not flash)

1. Press and release each button to make sure that the correct lights come

ON for each relay. If the lights turn ON, verify that Sensitivity is on High.

2. Check the wire connections, in particular, the Line connection. Verify

that connections are tightly secured. 

3. If lights still do not turn ON, call 800.879.8585 for technical support.

ADJUSTMENTS

Sensor Adjustment

Remove the wall plate. Remove the button cap by firmly squeezing together the
top sides of the button assembly. Gently pull it away from the unit. 

When the adjustments are completed, replace the button cap by inserting its
hinges into the tabs on the main unit and then squeeze the top of the button while
pressing it into the unit. Reinstall the cover plate.

Light Level Adjustment

The light level can be set with loads ON or OFF. To enable light level control and
set the threshold: 1) Make sure the room is lit appropriately. 2) Put the sensor into
TEST mode. You have 5 minutes to complete the procedure. 3) Press and hold the
ON/OFF button (Relay 

1

button on the PW-200) for 3 seconds, until you hear a

beep. 4) Step away from the sensor. After 25 seconds a beep sounds, indicating
that the threshold level is set. This threshold is retained, even if power is lost,
until it is re-set or disabled. In the PW-200, light level control only affects Relay 

2

To disable light level control, press and hold the Relay 

1

button for 

7 seconds

,

until a double beep tone sounds.

Reset to Default

To reset the PW to factory settings, press and hold the Relay 

1

button for 

10

seconds

, until a triple beep sounds. This resets the sensor occupancy history and

disables light level control (the brightest ambient light will not hold the light OFF).

Summary of Contents for PW-100

Page 1: ...andescent fluorescent magnetic or electronic ballast Horsepower Rating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec at initial power up or DIP switch reset PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual US Patents 5640113 6617560B2 A4787722 A4874962...

Page 2: ...using the ON OFF button Auto ON DIP 8 OFF for Relay 1 DIP 9 OFF for Relay 2 Load turns ON and OFF automatically based on occupancy If the load is turned OFF manually it stays OFF until 5 minutes after the last occupancy detection at which time it reverts to Auto ON mode This prevents the load from turning ON automatically after it was deliberately turned OFF Pressing the button to turn lights ON r...

Page 3: ...tes if the space is usually vacant up to 30 minutes if the space gets heavy usage SmartSet behavior starts immediately and is refined continually as history is collected A Test Mode with a short time delay of 5 seconds is set when DIP switches 1 2 3 are OFF It cancels automatically after five minutes or when you set a fixed time delay To restart Test Mode change the time delay setting to any fixed...

Page 4: ...s PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Alerts The PW can provide audible and or visible alerts as a warning before the load turns OFF Whistles twice at one minute and at 30 seconds before turning OFF load Chirps 10 seconds before turning OFF load Beeps three times 10 seconds before the load goes OFF for Walk Through If Visible Alert is also ON the one minute whi...

Page 5: ...ush the Auto ON OFF switch for each load and the lights will turn ON There is a delay due to initial power up of the sensor that only occurs during installation 5 Test and adjust the sensor if necessary 6 Attach the cover plate INSTALLATION Neutral Blue Line Black Secondary Load Brown Primary Load Red Ground Green Blue Primary Load Secondary Load Neutral Red Brown Line 2 Line 1 Neutral Ground Gree...

Page 6: ...e Alert 4 Disabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Auto Test 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes override 5 minutes 1 2 3 Time Delay Bypass occupancy light level functions Loads are manually controlled with PW 200 buttons 6 Disabled Enabled Visible Alert PW 200 ONLY Call 800...

Page 7: ...the top sides of the button assembly Gently pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit Reinstall the cover plate Light Level Adjustment The light level can be set with loads ON or OFF To enable light level control and set the thresh...

Page 8: ... 277VAC 50 60Hz PW 100 347 Passive infrared wall switch sensor 347VAC 50 60Hz PW 200 Passive infrared dual relay wall switch sensor 120 230 277VAC 50 60Hz ASP 422 Blank cover plate for 2 gang box ASP 432 Switch option cover plate for 2 gang box Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then...

Reviews: