1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the PW flying leads as shown in the
wiring diagram that is appropriate to the PW model and
electrical supply.
The ground wire (green) must be
festened to ground for the sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into
the two wide holes on the top and bottom of the attached
metal bracket. Match them up with the
holes in the wall box and tighten.
4. Turn the circuit breaker ON. Wait one
minute, then push the Auto ON/OFF switch
for each load and the lights will turn ON.
There is a delay due to initial power-up of
the sensor that only occurs during
installation.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
INSTALLATION
Neutral
Blue
Line
Black
Secondary
Load
Brown
Primary
Load
Red
Ground
Green
Blue
Primary
Load
Secondary
Load
Neutral
Red
Brown
Line 2
Line 1
Neutral
Ground
Green
Black
PW-200 Bi-Level Wiring
PW-200 Dual Circuit Wiring
WARNING
TURN THE POWER OFF AT THE CIRCUIT BREAKER
BEFORE INSTALLING THE SENSOR OR WORKING ON THE LOAD.
!
#12 – #14 AWG
Cu Wire Only
Strip Gage
1/2"
12.7mm
Visit our website for FAQs: www.wattstopper.com
Load
Red
Line Black
Neutral
Ground
Green
PW-100 and PW-100-347 Wiring