UNIT DESCRIPTION AND OPERATION

The PW Passive Infrared Wall Switch sensors use advanced passive infrared
(PIR) technology.  

The PW sensor can turn a load on, and hold it on as long as the sensor detects
occupancy. After no movement is detected for the selected time delay, the lights
switch off. A “walk-through” mode can turn lights off after only 3 minutes, if no
activity is detected after 30 seconds following an occupancy detection.

The PW-100 has one relay and one ON/OFF button. The PW-200 contains two
relays and two ON/OFF buttons to allow control of one or two loads
independently. Pressing a button toggles the state of the corresponding relay. 

PW sensors contain a light level sensor. If adequate daylight is present, the
sensor holds the load OFF until light levels drop, even if the area is occupied. In
the PW-200, light level only affects the load on Relay 2. Users can override this
function by pressing the ON/OFF button. See Light Level Adjustment.

Turning The Load ON

The relays are programmed independently for either Auto ON or Manual ON. In
either mode, the load can be turned ON or OFF using the ON/OFF button.

Auto ON 

DIP 8 OFF
for Relay 1

DIP 9 OFF
for Relay 2

Load turns ON and OFF automatically based on occupancy. If the
load is turned OFF manually, it stays OFF until 5 minutes after
the last occupancy detection, at which time it reverts to Auto ON
mode. This prevents the load from turning ON automatically
after it was deliberately turned OFF. Pressing the button to turn
lights ON returns the sensor to Auto ON mode. 

**

PW-100: Switch 9 is not used. PW-200: Switch 9 default is ON to comply
with CA Energy Commission Title 24 bi-level switching requirements.

Time Delays

The PW sensor holds the load ON until no motion is detected for the selected
time delay. Select the time delay using DIP switch settings. The sensor
automatically sets the time delay when SmartSet is enabled. In the PW-200,
both relays use the same delay.

Manual ON

DIP 8 ON
for Relay 1

DIP 9

**

ON

for Relay 2

Occupants must press the ON/OFF button to turn ON the load.
The sensor keeps the load ON until no motion is detected for the
selected time delay. There is a 30 second re-retrigger delay. If
occupancy is detected during the delay, the sensor turns the load
back ON. After the re-trigger delay elapses the ON/OFF button
must be pressed to turn ON the load.

Shading indicates default operation and switch setting. 

Summary of Contents for PW-100

Page 1: ...andescent fluorescent magnetic or electronic ballast Horsepower Rating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec at initial power up or DIP switch reset PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual US Patents 5640113 6617560B2 A4787722 A4874962...

Page 2: ...using the ON OFF button Auto ON DIP 8 OFF for Relay 1 DIP 9 OFF for Relay 2 Load turns ON and OFF automatically based on occupancy If the load is turned OFF manually it stays OFF until 5 minutes after the last occupancy detection at which time it reverts to Auto ON mode This prevents the load from turning ON automatically after it was deliberately turned OFF Pressing the button to turn lights ON r...

Page 3: ...tes if the space is usually vacant up to 30 minutes if the space gets heavy usage SmartSet behavior starts immediately and is refined continually as history is collected A Test Mode with a short time delay of 5 seconds is set when DIP switches 1 2 3 are OFF It cancels automatically after five minutes or when you set a fixed time delay To restart Test Mode change the time delay setting to any fixed...

Page 4: ...s PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Alerts The PW can provide audible and or visible alerts as a warning before the load turns OFF Whistles twice at one minute and at 30 seconds before turning OFF load Chirps 10 seconds before turning OFF load Beeps three times 10 seconds before the load goes OFF for Walk Through If Visible Alert is also ON the one minute whi...

Page 5: ...ush the Auto ON OFF switch for each load and the lights will turn ON There is a delay due to initial power up of the sensor that only occurs during installation 5 Test and adjust the sensor if necessary 6 Attach the cover plate INSTALLATION Neutral Blue Line Black Secondary Load Brown Primary Load Red Ground Green Blue Primary Load Secondary Load Neutral Red Brown Line 2 Line 1 Neutral Ground Gree...

Page 6: ...e Alert 4 Disabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Auto Test 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes override 5 minutes 1 2 3 Time Delay Bypass occupancy light level functions Loads are manually controlled with PW 200 buttons 6 Disabled Enabled Visible Alert PW 200 ONLY Call 800...

Page 7: ...the top sides of the button assembly Gently pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit Reinstall the cover plate Light Level Adjustment The light level can be set with loads ON or OFF To enable light level control and set the thresh...

Page 8: ... 277VAC 50 60Hz PW 100 347 Passive infrared wall switch sensor 347VAC 50 60Hz PW 200 Passive infrared dual relay wall switch sensor 120 230 277VAC 50 60Hz ASP 422 Blank cover plate for 2 gang box ASP 432 Switch option cover plate for 2 gang box Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then...

Reviews: