Fixed Time Delay

(DIP 1 ON, 2 & 3 OFF)

High 

(DIP #5 OFF)

Walk-Through
Mode

(DIP #4 ON)

The PW sensor turns the load OFF three minutes after
the area is initially occupied, if no motion is detected
after the first 30 seconds. If motion continues beyond
the first 30 seconds, the set time delay applies.

Default setting. Suitable for most applications.

PIR Sensitivity Adjustment

The PW sensor constantly monitors the controlled environment and
automatically adjusts the PIR to avoid common ambient conditions that can
cause false detections, while providing maximum coverage. 

Time delays are 5, 10, 15, 

20

(default), 25, or 30

minutes.

SmartSet™ auto
adjust time delay
and Test Mode 

Records typical occupancy patterns. Using this history
(which is constantly updated), it chooses an optimal
time delay from 7 minutes (if the space is usually
vacant) up to 30 minutes (if the space gets heavy
usage). SmartSet behavior starts immediately, and is
refined continually as history is collected.

A Test Mode with a short time delay of 5 seconds is set
when DIP switches 1, 2, & 3 are OFF. It cancels
automatically after five minutes, or when you set a
fixed time delay. To restart Test Mode, change the time
delay setting to any fixed amount and then return it to
the Auto/Test setting.

Reduces sensitivity by approximately 50%. Useful in
cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and
where heat sources cause unnecessary activation.

Low, 50%

(DIP #5 ON)

Visit our website for FAQs: www.wattstopper.com

Walk-Through

The Walk-Through mode shortens the time delay to reduce the amount of time
the load is ON after a brief moment of occupancy, such as returning to an office
to pick up a forgotten item then immediately exiting.

No Walk-Through

Walk-Through mode disabled.

Summary of Contents for PW-100

Page 1: ...andescent fluorescent magnetic or electronic ballast Horsepower Rating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec at initial power up or DIP switch reset PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual US Patents 5640113 6617560B2 A4787722 A4874962...

Page 2: ...using the ON OFF button Auto ON DIP 8 OFF for Relay 1 DIP 9 OFF for Relay 2 Load turns ON and OFF automatically based on occupancy If the load is turned OFF manually it stays OFF until 5 minutes after the last occupancy detection at which time it reverts to Auto ON mode This prevents the load from turning ON automatically after it was deliberately turned OFF Pressing the button to turn lights ON r...

Page 3: ...tes if the space is usually vacant up to 30 minutes if the space gets heavy usage SmartSet behavior starts immediately and is refined continually as history is collected A Test Mode with a short time delay of 5 seconds is set when DIP switches 1 2 3 are OFF It cancels automatically after five minutes or when you set a fixed time delay To restart Test Mode change the time delay setting to any fixed...

Page 4: ...s PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Alerts The PW can provide audible and or visible alerts as a warning before the load turns OFF Whistles twice at one minute and at 30 seconds before turning OFF load Chirps 10 seconds before turning OFF load Beeps three times 10 seconds before the load goes OFF for Walk Through If Visible Alert is also ON the one minute whi...

Page 5: ...ush the Auto ON OFF switch for each load and the lights will turn ON There is a delay due to initial power up of the sensor that only occurs during installation 5 Test and adjust the sensor if necessary 6 Attach the cover plate INSTALLATION Neutral Blue Line Black Secondary Load Brown Primary Load Red Ground Green Blue Primary Load Secondary Load Neutral Red Brown Line 2 Line 1 Neutral Ground Gree...

Page 6: ...e Alert 4 Disabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Auto Test 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes override 5 minutes 1 2 3 Time Delay Bypass occupancy light level functions Loads are manually controlled with PW 200 buttons 6 Disabled Enabled Visible Alert PW 200 ONLY Call 800...

Page 7: ...the top sides of the button assembly Gently pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit Reinstall the cover plate Light Level Adjustment The light level can be set with loads ON or OFF To enable light level control and set the thresh...

Page 8: ... 277VAC 50 60Hz PW 100 347 Passive infrared wall switch sensor 347VAC 50 60Hz PW 200 Passive infrared dual relay wall switch sensor 120 230 277VAC 50 60Hz ASP 422 Blank cover plate for 2 gang box ASP 432 Switch option cover plate for 2 gang box Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then...