Fixed Time Delay
(DIP 1 ON, 2 & 3 OFF)
High
(DIP #5 OFF)
Walk-Through
Mode
(DIP #4 ON)
The PW sensor turns the load OFF three minutes after
the area is initially occupied, if no motion is detected
after the first 30 seconds. If motion continues beyond
the first 30 seconds, the set time delay applies.
Default setting. Suitable for most applications.
PIR Sensitivity Adjustment
The PW sensor constantly monitors the controlled environment and
automatically adjusts the PIR to avoid common ambient conditions that can
cause false detections, while providing maximum coverage.
Time delays are 5, 10, 15,
20
(default), 25, or 30
minutes.
SmartSet™ auto
adjust time delay
and Test Mode
Records typical occupancy patterns. Using this history
(which is constantly updated), it chooses an optimal
time delay from 7 minutes (if the space is usually
vacant) up to 30 minutes (if the space gets heavy
usage). SmartSet behavior starts immediately, and is
refined continually as history is collected.
A Test Mode with a short time delay of 5 seconds is set
when DIP switches 1, 2, & 3 are OFF. It cancels
automatically after five minutes, or when you set a
fixed time delay. To restart Test Mode, change the time
delay setting to any fixed amount and then return it to
the Auto/Test setting.
Reduces sensitivity by approximately 50%. Useful in
cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and
where heat sources cause unnecessary activation.
Low, 50%
(DIP #5 ON)
Visit our website for FAQs: www.wattstopper.com
Walk-Through
The Walk-Through mode shortens the time delay to reduce the amount of time
the load is ON after a brief moment of occupancy, such as returning to an office
to pick up a forgotten item then immediately exiting.
No Walk-Through
Walk-Through mode disabled.